A transmission line of 210 km length has certain values of parameters A, B, C, D. If the length is made 100 km thus the parameter
C increases D decreases
C and D both decrease
C and D both increase
C decreases D increases
C decreases D increases
D is correct because as the length of the transmission line decreases, the shunt admittance parameter C decreases, and the voltage transformation parameter D also decreases towards unity.
Original transmission line length l1 = 210 km, New transmission line length l2 = 100 km.
C=YsтАЛ=yl(1+6ZsтАЛYsтАЛтАЛ)тЙИyl, D=A=1+2YZтАЛтЙИ1+2yzl2тАЛ
Analyze Parameter C
For a transmission line, the shunt admittance parameter C is approximately proportional to the length of the line (l) since CтЙИyl, where y is the shunt admittance per unit length.
CтИЭl
Analyze Parameter D
The parameter D (and A) for a transmission line is given by DтЙИ1+2yzl2тАЛ. As the length l decreases, the term l2 decreases significantly, causing the value of D to decrease relative to the increase in shunt impedance effects.
DтЙИ1+2yzl2тАЛ
Comparison of Changes
Since the length decreased from 210 km to 100 km, the parameter C (directly proportional to length) must decrease. Conversely, D approaches 1 as length decreases (the transmission line characteristics change as the line becomes electrically shorter).
CnewтАЛ<ColdтАЛ,DnewтАЛ<DoldтАЛ
D is correct because as the length of the transmission line decreases, the shunt admittance parameter C decreases, and the voltage transformation parameter D also decreases towards unity.
In power systems, parameter A and D are equal for symmetrical lines. Remember that for shorter lines, the network moves toward an ideal short circuit behavior (A, D тЖТ 1 and B, C тЖТ 0).