A transmission line of 210 km length has certain values of parameters A, B, C, D. If the length is made 100 km thus the parameter
A increase B decreases
A decreases B also decreases
A and B both increase
A decreases B increases
A increase B decreases
A is correct because for a transmission line, parameter A behaves like cosh(╬│l) which increases towards 1 as length decreases, and B is proportional to length, thus decreasing as length decreases.
A transmission line of length l = 210 km is reduced to l = 100 km.
A=cosh(╬│l),B=ZcтАЛsinh(╬│l)
Analyze Parameter A
For a long transmission line, the constant A is given by A=cosh(╬│l), where ╬│ is the propagation constant and l is the length. As l decreases, cosh(╬│l) approaches 1 from a value greater than 1, meaning A increases towards unity.
A=cosh(╬│l)тЙИ1+2(╬│l)2тАЛ
Analyze Parameter B
The series impedance parameter B is given by B=ZcтАЛsinh(╬│l). Since sinh(x)тЙИx for small x, B is approximately proportional to the length l. As l decreases, B decreases linearly.
BтЙИZcтАЛ╬│l
Conclusion
Comparing the behavior, as length l reduces, A moves closer to 1 (increases) and B reduces proportionally with length (decreases).
lтЖУтЯ╣AтЖС,BтЖУ
A is correct because for a transmission line, parameter A behaves like cosh(╬│l) which increases towards 1 as length decreases, and B is proportional to length, thus decreasing as length decreases.
In power systems, these ABCD parameters are derived from the transmission line telegrapher equations; remember that B represents the series impedance, which is always directly proportional to the length of the line.