An industrial installation has a power factor of 0.8 lagging. It would be economical to improve power factor to
Unity
About 0.8 leading
About 0.95 lagging
About 0.95 leading
About 0.95 lagging
Improving the power factor of an industrial installation to unity is technically possible but often economically unviable due to the diminishing returns of capacitor bank sizing. Improving the power factor to about 0.95 lagging is considered the economic optimum because it balances the reduction in I2R losses and penalty avoidance against the increasing cost of corrective equipment required to reach near-unity.
Improving the power factor of an industrial installation to unity is technically possible but often economically unviable due to the diminishing returns of capacitor bank sizing. Improving the power factor to about 0.95 lagging is considered the economic optimum because it balances the reduction in I2R losses and penalty avoidance against the increasing cost of corrective equipment required to reach near-unity.
QcтАЛ=P(tan╧Х1тАЛтИТtan╧Х2тАЛ) тАФ where QcтАЛ is required capacitive reactive power
P=VIcos╧Х тАФ where P is active power and cos╧Х is the power factor
The industrial load is typically inductive, characterized by P=VIcos╧Х. Adding shunt capacitors provides leading reactive power QcтАЛ, neutralizing the lagging reactive power QLтАЛ of the motor loads. The economic limit is reached when the marginal cost of adding more capacitance exceeds the marginal savings generated by reduced billing penalties and lower distribution system losses.
Unity power factor requires infinite or very large capacitor banks for incremental gain.
Most electricity distribution companies impose penalties if the power factor falls below 0.9 or 0.95.
Correcting to 0.95 lagging avoids penalties without the excessive cost of over-correction.
Over-correction leads to leading power factor, which can cause voltage instability.
Reduced I2R copper losses in cables and transformers
Improved voltage regulation
Avoidance of heavy utility penalties
Increased effective capacity of existing equipment
Risk of resonance if harmonics are present
Leading power factor may cause voltage rise at the consumer end
Industrial induction motor banks
Distribution transformers
Manufacturing plant power distribution
Option A is incorrect because while unity is the 'ideal' electrical state, it is rarely the most 'economical' due to equipment cost.
Option D is incorrect because leading power factor can cause dangerous over-voltage conditions.
Power factor correction is usually performed locally at the load for induction motors.
C is correct тАФ Improving to 0.95 lagging provides the best economic balance between loss reduction, penalty avoidance, and capital expenditure.
Always remember that in competitive exams, 'economical' implies a cost-benefit analysis, not just an ideal performance parameter.