The most suitable location of a power factor improvement device is
Near the electrical appliances which is responsible for poor power factor
At the receiving end in case of transmission line
At the sending end
Both (a) and (b)
Both (a) and (b)
Power factor improvement devices like static capacitors are most effective when placed near the inductive load to neutralize reactive power locally. Placing them at the receiving end of a transmission line also helps compensate for the reactive power drop across the line impedance, thereby improving the voltage profile at the load.
Power factor improvement devices like static capacitors are most effective when placed near the inductive load to neutralize reactive power locally. Placing them at the receiving end of a transmission line also helps compensate for the reactive power drop across the line impedance, thereby improving the voltage profile at the load.
QcтАЛ=P(tan╧Х1тАЛтИТtan╧Х2тАЛ) тАФ Reactive power to be provided by capacitor to improve power factor from cos╧Х1тАЛ to cos╧Х2тАЛ
InewтАЛ=cos╧Х2тАЛIoldтАЛcos╧Х1тАЛтАЛ тАФ Reduced line current after improvement
Inductive loads draw lagging reactive power (Q=VIsin╧Х). By connecting a capacitor in parallel, the capacitor supplies leading reactive power (QcтАЛ) locally. This reduces the total reactive current drawn from the source, minimizing I2R losses and voltage drops (VdropтАЛтЙИIrтАЛR+IxтАЛX) in the line.
Localized compensation (at load) prevents line losses between source and load.
System-level compensation (receiving end) helps maintain bus voltage stability.
Capacitors are the most common device for power factor improvement.
Over-correction leads to a leading power factor, which can increase system voltage dangerously.
Reduces I2R copper losses
Increases available active power capacity of the system
Improves voltage regulation
Reduces electricity billing penalties for low power factor
Sensitive to harmonic distortion
Risk of resonance if not properly tuned
Switching transients during capacitor bank connection
Industrial motor drives
Transmission and distribution substations
Commercial building HVAC systems
Option A is ideal for minimizing losses in distribution feeders.
Option B is essential for long transmission lines to maintain receiving-end voltage stability.
Option D represents the best engineering practice by covering both local and systemic levels.
D is correct тАФ The most suitable location is near the inductive load to minimize transmission losses, and at the receiving end to maintain terminal voltage stability.
Always remember that power factor improvement is essentially the injection of reactive power (Q) to reduce the net reactive power demand from the source, effectively increasing the system's efficiency.