Advantage of improved power factor is
Increase in operating efficiency of power system
Improvement in voltage regulation
Reduction in overall cost per unit
Better utilization of kW capacity of prime movers, transformers, switchgears and line
Better utilization of kW capacity of prime movers, transformers, switchgears and line
Improving the power factor reduces the reactive power demand of a load, which directly decreases the total apparent power (kVA) drawn from the source for the same amount of active power (kW). This allows electrical infrastructure like transformers and lines to be utilized for supplying more productive real power rather than carrying unnecessary reactive current.
Improving the power factor reduces the reactive power demand of a load, which directly decreases the total apparent power (kVA) drawn from the source for the same amount of active power (kW). This allows electrical infrastructure like transformers and lines to be utilized for supplying more productive real power rather than carrying unnecessary reactive current.
P=VIcos╧Х тАФ Active power (kW)
S=VI тАФ Apparent power (kVA)
kVA=cos╧ХkWтАЛ тАФ Relationship showing that as cos╧Х increases, kVA decreases for constant kW
The apparent power is defined as S=P2+Q2тАЛ. When power factor (cos╧Х) is improved, the reactive power component (Q) decreases for a fixed real power (P). Since transmission and distribution equipment ratings are based on apparent power (kVA=cos╧ХkWтАЛ), decreasing the kVA requirement effectively increases the 'available' capacity of the system to serve more loads without upgrading existing equipment.
Improved power factor results in lower line currents for the same power delivery.
Lower currents lead to reduced I2R copper losses in the transmission and distribution network.
Better voltage regulation is achieved due to reduced voltage drops in lines (VdropтАЛтЙИI(Rcos╧Х+Xsin╧Х)).
It avoids penalties imposed by electricity utilities for low power factor operation.
Reduced conductor size requirement
Lower copper losses in the system
Improved voltage regulation
Increased system capacity
Initial cost of capacitors or synchronous condensers
Maintenance requirement for power factor correction equipment
Industrial plants with induction motors
Large commercial buildings
Distribution substations
Standard power factor is generally required to be maintained above 0.95 by most utilities to avoid financial surcharges.
Option A (Operating Efficiency) is a result of lower I┬▓с┤┐ losses, and Option B (Voltage Regulation) is a result of lower voltage drop, but Option D represents the most fundamental capacity-related benefit in system design.
D is correct тАФ Improved power factor reduces the kVA demand, allowing the existing kW capacity of transformers, switchgear, and lines to be utilized more effectively.
Always remember: low power factor is equivalent to high reactive power flow; improving it is essentially 'cleaning up' the current flow so that more of the transmission capacity is used for real work (kW) rather than oscillating reactive energy.