Belted type construction is not suitable for cables used for voltages exceeding 22 kV because of
Development of both radial and tangential stresses
Formation of vacuous and voids on loading and unloading owning to owing to non-homogeneity of dielectric in belted construction
Local heating caused by power loss at centre filling owning to leakage current produced by tangential stresses along the impregnated paper insulation resulting in breakdown it anytime
All of above
All of above
Belted-type cables are unsuitable for voltages exceeding 22 kV because the insulation is composed of layers of impregnated paper that experience both radial and tangential stresses. At higher voltages, these stresses lead to dielectric breakdown due to the non-homogeneous nature of the insulation.
Belted-type cables are unsuitable for voltages exceeding 22 kV because the insulation is composed of layers of impregnated paper that experience both radial and tangential stresses. At higher voltages, these stresses lead to dielectric breakdown due to the non-homogeneous nature of the insulation.
EradialтАЛ=xln(R/r)VтАЛ тАФ radial electric field intensity at distance x from center
VmaxтАЛ=3тАЛEmaxтАЛтЛЕrln(R/r)тАЛ тАФ maximum operating voltage limit for belted design
In a belted cable, the three conductors are bundled with paper insulation, and a common belt of paper is wrapped around all three. Because the electric field is not purely radial, tangential stress is produced along the layers of paper. Since impregnated paper is much weaker along the laminations than across them, this tangential stress causes internal discharges, leading to ionization, void formation, and eventual thermal breakdown.
Belted cables utilize a common belt of impregnated paper insulation for all three conductors.
The presence of tangential stress is the primary limiting factor, as dielectric strength is lowest along the paper layers.
Ionization in the voids leads to permanent damage known as treeing, which eventually punctures the insulation.
H-type or S.L. cables are used for voltages above 22 kV to eliminate tangential stresses.
Simple manufacturing process
Economical for low-voltage power distribution
Compact design due to common belt
High tangential stress leading to dielectric failure
Formation of voids due to load cycling
Not suitable for high-voltage applications (> 22 kV)
Low-voltage distribution feeders
Industrial plant cabling (internal)
Sub-transmission networks up to 11 kV or 22 kV
The 22 kV limit is a practical standard; beyond this, the tangential stress component dominates the design criteria.
Option B refers to the 'breathing' effect where cyclic loading causes the compound to expand and contract, creating voids.
D is correct тАФ All the mentioned factors contribute to the unsuitability of belted cables for high-voltage applications.
Always remember that H-type (Hochstadter) cables were invented specifically to convert tangential stress into radial stress using metallic screens, effectively solving the problems associated with belted construction.