Join 60,000+ competitive exam aspirants
Booster is connected in
Parallel with the feeder
Series with the feeder
Either (a) or (b)
None of above
Series with the feeder
A feeder booster is a transformer used to compensate for voltage drops along a distribution feeder. It is connected in series with the feeder line to inject an additional voltage boost proportional to the line current, ensuring the voltage at the load end remains within permissible limits.
A feeder booster is a transformer used to compensate for voltage drops along a distribution feeder. It is connected in series with the feeder line to inject an additional voltage boost proportional to the line current, ensuring the voltage at the load end remains within permissible limits.
VoutтАЛ=VinтАЛ+VboostтАЛ тАФ Voltage compensation principle
VboostтАЛтИЭIfeederтАЛ тАФ Voltage boost magnitude depends on feeder current
The booster transformer has its primary winding connected in shunt across the feeder (sensing the voltage) and its secondary winding connected in series with the feeder. The induced secondary voltage adds to the existing line voltage, thereby compensating for the I├ЧZ drop along the feeder. Since the compensation is dependent on the magnitude of the current, these are often referred to as series boosters.
Used to improve voltage regulation in long distribution feeders.
Operates as an auto-transformer where the secondary is in series with the line.
Usually equipped with an On-Load Tap Changer (OLTC) for automated control.
Prevents voltage drop due to ohmic resistance and inductive reactance of the line.
Cost-effective way to improve voltage profile compared to re-conductoring.
Allows for independent voltage control on specific branches of a distribution network.
Introduces additional impedance into the circuit.
Requires maintenance of the tap-changing mechanism.
Rural distribution networks.
Long radial feeders where voltage regulation is poor.
Feeder boosters are critical in rural electrification projects where lines are excessively long, causing significant voltage drops.
Option A is incorrect because a parallel connection would short-circuit the feeder or cause excessive circulating currents, making it unsuitable for voltage boost applications.
B is correct тАФ The booster transformer is connected in series with the feeder to inject voltage to compensate for the I├ЧZ drop.
Always remember that 'Series' devices (boosters, CTs) affect the current or add voltage along the line, while 'Shunt' devices (capacitors, PTs) affect the voltage across the line.