Compared with a solid conductor of the same radius, corona appears on a stranded conductor at a lower voltage, because stranding
Assists ionization
Makes the current flow spirally about the axis of the conductor
Produces oblique sections to a plane perpendicular to the axis of the conductor
Produces surfaces of smaller radius
Produces oblique sections to a plane perpendicular to the axis of the conductor
Corona inception occurs when the surface electric field intensity exceeds the dielectric strength of air. Stranded conductors consist of individual strands that create a non-uniform surface, resulting in higher local electric field intensity compared to a perfectly smooth solid conductor of the same overall radius.
Corona inception occurs when the surface electric field intensity exceeds the dielectric strength of air. Stranded conductors consist of individual strands that create a non-uniform surface, resulting in higher local electric field intensity compared to a perfectly smooth solid conductor of the same overall radius.
E=rln(D/r)VтАЛ тАФ Electric field intensity at the surface of a conductor
VcтАЛ=g0тАЛтЛЕmтЛЕ╬┤тЛЕrтЛЕln(rDтАЛ) тАФ Critical disruptive voltage where m<1 for stranded conductors
In a stranded conductor, the outer surface is not perfectly cylindrical but presents a series of oblique sections relative to a cross-sectional plane. This irregular surface geometry concentrates the electric flux lines, causing the localized surface potential gradient (E) to rise above the critical disruptive voltage (VcтАЛ) sooner than it would on a smooth solid surface.
Corona is a localized breakdown of air near high-voltage conductors.
Surface irregularity (roughness) increases the local electric field concentration.
Stranded conductors are used to increase flexibility and cross-sectional area, but they suffer more from corona than equivalent solid conductors.
The irregularity factor (m) is always less than 1 for stranded conductors, reducing the disruptive voltage threshold.
High flexibility for overhead lines
Easier installation and lower mechanical fatigue
Higher corona loss compared to smooth conductors
Increased electromagnetic interference (EMI) due to ionization
High Voltage AC (HVAC) transmission lines
Extra High Voltage (EHV) distribution systems
The irregularity factor 'm' accounts for surface conditions: m=1 for polished solid, m=0.82тИТ0.87 for stranded conductors.
Option A is incorrect as stranding does not assist ionization; it is an effect of the surface geometry. Option B and D are physically incorrect descriptions of the phenomenon.
C is correct тАФ Stranding produces oblique surface sections which increase local surface electric field intensity, lowering the voltage required to trigger corona discharge.
Always remember that corona is inversely proportional to the radius of curvature; sharper surfaces (or more irregular ones) lead to higher electric field concentration and earlier corona inception.