Join 60,000+ competitive exam aspirants
The charging current in a transmission line increases due to corona effect because corona increases
Line current
Effective line voltage
Power loss in lines
Effective conductor diameter
Effective conductor diameter
The corona effect creates a conductive ionized sheath around the conductor, which effectively increases its physical radius. Since the capacitance of a transmission line is inversely proportional to the natural logarithm of the ratio of spacing to the conductor radius, an increase in effective radius increases the capacitance, thereby increasing the charging current.
The corona effect creates a conductive ionized sheath around the conductor, which effectively increases its physical radius. Since the capacitance of a transmission line is inversely proportional to the natural logarithm of the ratio of spacing to the conductor radius, an increase in effective radius increases the capacitance, thereby increasing the charging current.
C=ln(D/r)2╧А╧╡0тАЛтАЛ тАФ Capacitance of a single-phase transmission line
IcтАЛ=j╧ЙCV тАФ Charging current in a transmission line
When the electric field strength at the conductor surface exceeds the breakdown strength of air (approx. 30 kV/cm), ionization occurs. This ionized region acts as a virtual conductor, increasing the effective diameter (d'). According to the formula C=ln(D/r)2╧А╧╡тАЛ, where r is the effective radius, an increase in r leads to higher capacitance (C). Because charging current IcтАЛ=VтЛЕ2╧АfC, an increase in C results in a higher charging current.
Corona is a localized breakdown of air around conductors.
Ionization increases the effective diameter of the conductor.
Increased effective diameter reduces the potential gradient at the surface but increases shunt capacitance.
Higher capacitance leads to increased charging current (IcтАЛ = V тЛЕ╧ЙC).
Reduces the intensity of the electric field at the conductor surface.
Helps in reducing the surge voltage magnitude during transient conditions.
Power loss (Corona loss) increases significantly.
Causes ozone production leading to chemical corrosion.
Generates radio frequency interference and audible noise.
The effective diameter is defined as the physical diameter of the conductor plus the thickness of the ionized corona sheath.
Options A, B, and C are incorrect because charging current is a consequence of shunt capacitance and applied voltage, not directly caused by the line current or power loss.
D is correct тАФ The corona effect increases the effective diameter of the conductor, which leads to an increase in the shunt capacitance, thereby increasing the charging current.
Always remember that corona effect increases capacitance, which is why long, extra-high-voltage (EHV) lines face higher Ferranti effect concerns due to increased charging currents.