Cradle guards are provided on the road crossing for the safety of the
Power line itself
Human beings, animals and material moving on the road
Both (a) and (b)
Neither (a) and (b)
Human beings, animals and material moving on the road
Cradle guards are mechanical protective structures installed below overhead transmission lines at points where they cross roads, railways, or public thoroughfares. Their primary purpose is to catch a broken conductor in the event of failure, preventing it from falling onto the road and causing electrical hazards.
Cradle guards are mechanical protective structures installed below overhead transmission lines at points where they cross roads, railways, or public thoroughfares. Their primary purpose is to catch a broken conductor in the event of failure, preventing it from falling onto the road and causing electrical hazards.
IfaultтАЛ=ZloopтАЛVphтАЛтАЛ тАФ Fault current magnitude during contact with cradle
TsтАЛтЙИ8dwL2тАЛ тАФ Mechanical tension in the conductor affecting breakage probability
The cradle guard consists of a lattice of grounded metallic wires suspended beneath the line conductors. If an overhead conductor snaps due to mechanical stress or storm damage, it falls onto the earthed cradle instead of live traffic. This results in an immediate earth fault, triggering protective relays (like overcurrent or earth-fault relays) at the substation to de-energize the line before it can cause harm to people or property on the road.
Cradle guards must be solidly grounded to ensure rapid fault clearing.
Required by safety regulations (IE Rules) for high-voltage crossings.
Provides physical separation between the conductor and the road surface.
Material is typically galvanized steel wire mesh.
Prevents fatal electric shocks to public/animals.
Minimizes damage to vehicles on the road.
Ensures automatic fault detection via relay tripping.
Adds weight to the support structures.
Requires regular inspection for corrosion.
Increases the aesthetic impact of the crossing.
Road crossings
Railway track crossings
Navigable river crossings
Public walkways near substations
Cradle guards are mandatory under the Indian Electricity Rules for lines passing over public roads if the safety clearance is compromised or as a secondary safety measure.
Option A is incorrect because the cradle guard is not intended to protect the line itself, but rather to mitigate the external impact of line failure.
B is correct тАФ Cradle guards are specifically designed to catch broken conductors to protect public life and property moving on the road.
Always remember that cradle guards are a passive mechanical safety device, whereas relays and circuit breakers are active electrical safety devices; they work in tandem to ensure system safety.