Effect of capacitance can be neglected when the length of overhead transmission line does not exceed
20 km
60 km
120 km
300 km
60 km
In electrical power transmission, the shunt capacitance of overhead lines is distributed along the entire length. For short transmission lines (typically defined as those under 60-80 km in length), the effect of this capacitance is negligible, allowing the line to be represented as a simple lumped series impedance consisting of resistance and inductance.
In electrical power transmission, the shunt capacitance of overhead lines is distributed along the entire length. For short transmission lines (typically defined as those under 60-80 km in length), the effect of this capacitance is negligible, allowing the line to be represented as a simple lumped series impedance consisting of resistance and inductance.
ZseriesтАЛ=R+j╧ЙL тАФ Total series impedance per phase
IchargingтАЛ=VphaseтАЛ├Чj╧ЙC тАФ Charging current neglected in short lines
The transmission line is modeled based on its length and voltage level. For 'Short' lines (length < 80 km), the charging current (Ic = V * ╧Й * C) is very small relative to the load current and can be ignored without significant error. As line length increases, the capacitive reactance (Xc = 1 / (2 * ╧А * f * C)) becomes low enough that shunt currents significantly affect voltage regulation and transmission efficiency, requiring more complex Pi or T-network models.
Short Transmission Lines: Length < 80 km, use series R and L model.
Medium Transmission Lines: 80 km < Length < 200 km, use nominal ╧Аor T model.
Long Transmission Lines: Length > 200 km, use rigorous distributed parameter equations.
The 60-80 km range is the standard threshold taught in competitive engineering examinations for neglecting shunt effects.
Simplifies power flow calculations
Reduces computational complexity for radial distribution networks
Inaccurate for long distance high voltage (EHV) lines
Neglects Ferranti effect which occurs at no-load/light-load in longer lines
Distribution systems
Short distance sub-transmission lines
While some textbooks specify 80 km, 60 km is widely used in objective-type examinations to represent the conservative threshold for short lines.
Option A (20 km) is too short as a threshold, while Options C (120 km) and D (300 km) require consideration of shunt effects.
B is correct тАФ for overhead transmission lines of length less than 60-80 km, the shunt capacitance effect is negligible and the line is modeled as a short transmission line.
Always remember: Short lines are lumped circuits, medium lines are nominal circuits, and long lines are distributed parameter circuits.