For a given amount of power to be transmitted over a certain distance with fixed power loss, the volume of copper required is
Proportional to voltage
Inversely proportional to voltage
Inversely proportional to square of voltage and power factor
Proportional to square of voltage and power factor
Inversely proportional to square of voltage and power factor
The volume of copper required for a transmission line is inversely proportional to the square of the transmission voltage (V2) and the square of the power factor (cos╧Х). By increasing the transmission voltage, the current required to transmit a specific amount of power decreases, significantly reducing the cross-sectional area of the conductor needed to maintain a fixed power loss.
The volume of copper required for a transmission line is inversely proportional to the square of the transmission voltage (V2) and the square of the power factor (cos╧Х). By increasing the transmission voltage, the current required to transmit a specific amount of power decreases, significantly reducing the cross-sectional area of the conductor needed to maintain a fixed power loss.
P=3тАЛVIcos╧Х тАФ Three-phase power equation
VolumeтИЭV2cos2╧Х1тАЛ тАФ Relation between volume, voltage, and power factor
For a fixed power P and power factor cos╧Х, the line current I is given by I=3тАЛVcos╧ХPтАЛ. The power loss W in a three-phase system is W=3I2R, where R=╧БAlтАЛ. Substituting I and R into the loss equation, we get W=3(3тАЛVcos╧ХPтАЛ)2(╧БAlтАЛ)=V2cos2╧ХAP2╧БlтАЛ. Rearranging for volume VolтАЛ=AтЛЕl, we find VolтАЛ=WV2cos2╧ХP2╧Бl2тАЛ. Thus, volume is inversely proportional to V2 and cos2╧Х.
Higher transmission voltage leads to lower line currents for the same power.
Lower currents allow for smaller conductor cross-sections, saving material costs.
The power factor affects the current; a lagging power factor increases the current, requiring more copper volume.
Fixed power loss is the design constraint used for determining conductor size.
Higher efficiency at high voltages
Reduced material cost due to smaller conductor diameter
Higher insulation costs at higher voltages
Increased risk of corona discharge
High Voltage Transmission (HVAC/HVDC)
Power grid infrastructure design
This derivation assumes line length, power delivered, and allowable power loss are constant.
Options A and B are incorrect because they define linear relationships rather than the quadratic inverse relationship required by the I2R power loss formula.
C is correct тАФ The volume of copper required for power transmission is inversely proportional to the square of the voltage and the square of the power factor.
Always remember that power loss is I2R; any variable that affects current I will have a squared impact on copper requirements.