For a single phase two wire line, the diameter is 1.213 cm and spacing is 1.25 m at 50 Hz. The loop inductance is
22.3×10−7 H/m
11.15×10−7 H/m
22.3×10−4 H/m
11.15×10−4 H/m
22.3×10−7 H/m
A is correct because the calculated loop inductance using the transmission line parameters is approximately 22.3×10−7 H/m.
Diameter of conductor d = 1.213 cm, Spacing between conductors D = 1.25 m, Frequency f = 50 Hz.
Lloop=4×10−7ln(r′D) H/m
Convert parameters to SI units
Radius r=d/2=1.213/2=0.6065 cm = 0.006065 m. GMR for solid conductor r′=0.7788r.
r′=0.7788×0.006065≈0.004723 m
Calculate the inductance ratio
Calculate the ratio r′D where D=1.25 m.
r′D=0.0047231.25≈264.66
Calculate Loop Inductance
Substitute values into Lloop=4×10−7ln(D/r′).
Lloop=4×10−7ln(264.66)≈4×10−7×5.578=22.31×10−7 H/m
A is correct because the calculated loop inductance using the transmission line parameters is approximately 22.3×10−7 H/m.
Remember that loop inductance is exactly twice the inductance per conductor (Lloop=2L), which is often used in power system analysis for single-phase circuits.