Join 60,000+ competitive exam aspirants
Presence of earth in case of overhead line
Increases the capacitance
Decreases the capacitance
Increases the inductance
Decreases the inductance
Increases the capacitance
The presence of earth acts as an equipotential plane near the overhead conductor, effectively introducing the 'Method of Images'. This configuration increases the potential difference between the conductor and the ground plane, which directly results in an increase in the total capacitance of the transmission line.
The presence of earth acts as an equipotential plane near the overhead conductor, effectively introducing the 'Method of Images'. This configuration increases the potential difference between the conductor and the ground plane, which directly results in an increase in the total capacitance of the transmission line.
C=ln(r2hтАЛ)2╧А╧╡0тАЛтАЛ тАФ Capacitance of a single conductor above ground
CeffтАЛ=CairтАЛ+CearthтАЛ тАФ Effective shunt capacitance increase
According to the method of images, an overhead conductor at height h above a conducting ground plane is electrically equivalent to the original conductor and a 'mirror image' conductor carrying the opposite charge at a depth h below the ground. The presence of this image charge increases the flux linkage path between the conductor and the ground, thereby increasing the shunt capacitance C=ln(2h/r)2╧А╧╡0тАЛтАЛ.
The ground acts as an equipotential surface, essentially behaving like a second plate in a capacitor.
The distance h between the conductor and ground is inversely proportional to the capacitance.
This phenomenon is specifically known as the 'Method of Images' in electromagnetic field theory.
Increasing the height h decreases the capacitance, whereas the proximity of the earth increases it.
Useful for calculating surge impedance loading.
Essential for analyzing ground return current paths in fault analysis.
Increases the charging current in long transmission lines.
Higher capacitance can lead to Ferranti effect concerns at light loads.
Power system steady-state analysis.
Protection relaying studies involving line charging currents.
The 'earth effect' is more significant in lower voltage lines where the conductors are relatively closer to the ground.
Option B is incorrect because capacitance is fundamentally increased by the proximity of any grounded conductor.
Options C and D are incorrect because the presence of earth primarily affects the electric field (capacitance) rather than the magnetic field (inductance) of the transmission line.
A is correct тАФ The presence of the earth plane creates an image charge that increases the total capacitance to ground.
Always remember that capacitance is defined by C=Q/V; when the earth acts as an image, it effectively provides a closer path for flux, increasing C for a given V.