Full load copper loss in a transformer is 1600 W. At half load the loss will be
400 W
1600 W
3200 W
6400 W
400 W
Copper loss in a transformer is directly proportional to the square of the current (load) flowing through the windings, defined by PcuтАЛ=I2R. Since load current I is directly proportional to the fractional load x, the copper loss varies as Pcu(x)тАЛ=x2├ЧPcu(full┬аload)тАЛ.
Copper loss in a transformer is directly proportional to the square of the current (load) flowing through the windings, defined by PcuтАЛ=I2R. Since load current I is directly proportional to the fractional load x, the copper loss varies as Pcu(x)тАЛ=x2├ЧPcu(full┬аload)тАЛ.
PcuтАЛ=x2PflтАЛ тАФ Copper loss at any fractional load x
x=Rated┬аFull┬аLoadActual┬аLoadтАЛ тАФ Definition of load factor
The copper loss (I2R loss) depends on the magnitude of the load current. When the transformer operates at a fraction of its rated capacity (x), the current becomes xIratedтАЛ. Consequently, the copper loss becomes (xIratedтАЛ)2R=x2(Irated2тАЛR), meaning the loss scales by the square of the load fraction.
Copper loss is variable loss as it changes with the square of the load.
Iron loss (Core loss) is considered constant regardless of the load variation.
At half load (x=0.5), losses decrease significantly due to the quadratic relationship.
Maximum efficiency occurs when constant (iron) losses equal variable (copper) losses.
Predictable loss calculation for varying load profiles
Essential for determining all-day efficiency of distribution transformers
High sensitivity to load changes
Does not account for stray load losses or harmonic distortion
Transformer efficiency rating
Calculation of distribution transformer performance under cyclic loading
For x=0.5, PcuтАЛ=(0.5)2├Ч1600=0.25├Ч1600=400┬аW.
Option B (1600 W) corresponds to full load.
Option C (3200 W) is a common error assuming linear instead of quadratic scaling.
Option D (6400 W) is the result of using 22 instead of (0.5)2.
A is correct тАФ The copper loss at half load is (0.5)2├Ч1600=400┬аW.
Remember that copper losses follow an x2 relationship, whereas efficiency curves are determined by the intersection of constant core losses and variable copper losses.