Identify starter type from the diagram given below.
Automatic DOL Starter
Automatic Primary Resistance Starter
Automatic Auto-transformer Starter
Automatic Star-Delta Starter
Automatic Star-Delta Starter
The correct answer is Option D, Automatic Star-Delta Starter. An automatic star-delta starter is used to reduce the high starting current of a three-phase induction motor by first connecting its stator windings in star configuration during startup and then switching them to delta configuration once the motor achieves near-rated speed. This switching is performed automatically using electromagnetic contactors and a time-delay relay (timer).
The correct answer is Option D, Automatic Star-Delta Starter. An automatic star-delta starter is used to reduce the high starting current of a three-phase induction motor by first connecting its stator windings in star configuration during startup and then switching them to delta configuration once the motor achieves near-rated speed. This switching is performed automatically using electromagnetic contactors and a time-delay relay (timer).
Vph,starтАЛ=3тАЛVLтАЛтАЛ тАФ Phase voltage across motor winding during Star connection
Ist,starтАЛ=31тАЛIst,DOLтАЛ тАФ Line starting current in Star connection compared to direct-on-line starting
Tst,starтАЛ=31тАЛTst,DOLтАЛ тАФ Starting torque in Star connection compared to direct-on-line starting torque
During startup, the main contactor and star contactor energize simultaneously, applying 3тАЛ1тАЛ times the line voltage to each phase winding, which reduces starting current to one-third of the direct-on-line (DOL) value. After a preset time delay, the timer de-energizes the star contactor and energizes the delta contactor, applying full line voltage across each phase winding for normal running operation.
Reduces starting current and starting torque to one-third (33.3%) of their respective DOL values.
Utilizes three contactors: Main Contactor, Star Contactor, and Delta Contactor, alongside a Time-Delay Relay (Timer).
Suitable for 3-phase induction motors that are designed to run normally in Delta connection.
Inexpensive and simple method compared to auto-transformer starters.
Effectively reduces heavy line current surges during motor startup.
Automatic transition ensures smooth operation without manual intervention.
Starting torque is reduced to one-third, making it unsuitable for heavy-load starting.
Can cause current spikes during transition from Star to Delta connection.
Requires six external terminals brought out from the motor winding.
Centrifugal pumps and fans
Air compressors and machine tools
Medium-power 3-phase squirrel cage induction motors
Option A (Automatic DOLStarter) applies full line voltage directly across the motor terminals at startup, causing high starting current (5 to 8 times rated current).
Option B (Automatic Primary Resistance Starter) inserts series resistors in the stator circuit to drop voltage, which dissipates energy as heat.
Option C (Automatic Auto-transformer Starter) reduces starting voltage via variable autotransformer taps, offering adjustable starting torque but at higher cost.
D is correct тАФ The schematic represents an Automatic Star-Delta Starter which uses contactors and a timer to switch motor windings from star at startup to delta during normal operation.
Remember that both starting current and starting torque in a star-delta starter drop by a factor of 3 (i.e., 1/3 of DOL values), because current and torque are proportional to voltage and square of voltage respectively (TstтАЛтИЭV2).