Identify starter type from the diagram given below.
Automatic DOL Starter
Automatic Primary Resistance Starter
Automatic Autotransformer Starter
Automatic Star-Delta Starter
Automatic Autotransformer Starter
An Automatic Autotransformer Starter reduces the starting voltage applied to a three-phase induction motor by using a tapped autotransformer. By reducing the applied stator voltage during starting to xV (where x is the tapping fraction), the starting current drawn from the motor terminals drops to xIscтАЛ, while the line starting current drawn from the supply reduces to x2IscтАЛ. Once the motor accelerates to a preset speed, a timer triggers contactors to bypass the autotransformer, connecting the motor directly across the full supply line.
An Automatic Autotransformer Starter reduces the starting voltage applied to a three-phase induction motor by using a tapped autotransformer. By reducing the applied stator voltage during starting to xV (where x is the tapping fraction), the starting current drawn from the motor terminals drops to xIscтАЛ, while the line starting current drawn from the supply reduces to x2IscтАЛ. Once the motor accelerates to a preset speed, a timer triggers contactors to bypass the autotransformer, connecting the motor directly across the full supply line.
VstтАЛ=xтЛЕVlineтАЛ тАФ Motor starting voltage at transformation ratio x
Ist(motor)тАЛ=xтЛЕIscтАЛ тАФ Motor starting current with autotransformer
Ist(line)тАЛ=x2тЛЕIscтАЛ тАФ Line starting current drawn from the main supply
TstтАЛ=x2тЛЕTflтАЛтЛЕ(IflтАЛIscтАЛтАЛ)2тЛЕsflтАЛ тАФ Starting torque developed in terms of full-load torque
During the starting phase, the starting contactor closes to energize the motor through a specified tap (typically 50%, 65%, or 80%) of an autotransformer, supplying a reduced line voltage xV. The reduced terminal voltage limits the heavy starting current surge to protect the supply mains and windings. A timing relay (or automatic sensor) automatically disconnects the autotransformer tap after a set time delay and switches over to the main running contactor, connecting the motor directly to full line voltage V.
Reduces line starting current by a factor of x2, making it more effective at limiting supply disturbances than primary resistance starters.
Provides flexibility through multiple transformer tapping points (typically 50%, 65%, and 80%).
Suitable for both Star and Delta connected three-phase induction motors.
Higher initial cost and larger physical footprint compared to DOL or Star-Delta starters due to the transformer winding.
Line starting current is reduced to x2IscтАЛ, minimizing voltage sags on the supply network.
Tapping options (50%, 65%, 80%) allow flexibility to adjust starting torque and current according to load conditions.
Can be used with both star-connected and delta-connected induction motors.
Expensive and bulky due to the requirement of an autotransformer coil assembly.
Lower power factor during the starting transient period.
More complex automatic control schematic using time-delay relays and multiple contactors.
Starting large 3-phase squirrel cage induction motors where Star-Delta starters cannot produce adequate starting torque.
Industrial drives requiring adjustable starting current limits such as high-inertia blowers, water pumps, and compressors.
Option A (Automatic DOLStarter) applies full supply voltage directly across motor terminals without voltage reduction, producing high starting current (5тИТ8├ЧIflтАЛ).
Option B (Automatic Primary Resistance Starter) uses series resistors in stator lines to drop voltage; line current equals motor current (IlineтАЛ=xIscтАЛ).
Option D (Automatic Star-Delta Starter) changes motor winding connection from Star to Delta, which fixes the voltage reduction to a constant ratio of 1/3тАЛ (57.7%).
C is correct тАФ The schematic represents an Automatic Autotransformer Starter, which utilizes an autotransformer with tapped outputs to step down the motor terminal voltage during automatic starting sequences.
Always remember for competitive exams: Line starting current in an autotransformer starter drops by x2, whereas in a primary resistance starter it drops by x. This makes autotransformer starting far superior in limiting supply line disturbances.