Identify starter type from the diagram given below.
Automatic DOL Starter
Automatic Primary Resistance Starter
Automatic Autotransformer Starter
Automatic Star-Delta Starter
Automatic Primary Resistance Starter
An Automatic Primary Resistance Starter reduces the starting current of a 3-phase induction motor by inserting external resistors directly in series with the stator primary windings during startup. As the motor accelerates and reaches a predetermined speed or time delay, a contactor/timer automatically shorts out the primary resistors, connecting full line voltage across the stator.
An Automatic Primary Resistance Starter reduces the starting current of a 3-phase induction motor by inserting external resistors directly in series with the stator primary windings during startup. As the motor accelerates and reaches a predetermined speed or time delay, a contactor/timer automatically shorts out the primary resistors, connecting full line voltage across the stator.
IstтАЛ=xтЛЕIscтАЛ тАФ Starting current with primary resistance, where x=VstтАЛ/VLтАЛ
TstтАЛ=x2тЛЕTscтАЛ тАФ Starting torque with primary resistance reduction factor x
At starting, the primary resistors drop a fraction of the line voltage, supplying a reduced voltage VstтАЛ to the motor stator to limit the initial heavy inrush current. As the motor speeds up, a timing relay energizes an automatic contactor that bypasses the primary resistors, restoring full line voltage VLтАЛ for normal running operation. This smooths out starting torque and prevents excessive supply voltage dips.
Reduces starting current proportional to the voltage reduction factor x.
Starting torque decreases with the square of the applied voltage (x2).
Power loss occurs in the primary resistors during the starting period.
Smooth acceleration with minimal current spikes.
Higher power factor during starting compared to autotransformer starting.
Simple control circuit layout using automatic timing relays.
Energy is wasted as heat in the starting primary resistors.
Low starting torque per ampere of starting current.
Squirrel cage induction motors where moderate starting torque is acceptable.
Applications requiring smooth acceleration to avoid mechanical shock (e.g., conveyors, light machine tools).
Option A (Automatic DOL Starter) applies full line voltage immediately, resulting in very high starting current.
Option C (Automatic Autotransformer Starter) uses a tapped transformer rather than series resistors to step down starting voltage.
Option D (Automatic Star-Delta Starter) changes the stator winding connection from Star at starting to Delta during running.
B is correct тАФ The schematic illustrates primary resistors inserted in series with the motor windings, which are automatically bypassed via contacts during acceleration.
Remember that both Primary Resistance and Autotransformer starters reduce voltage at starting, but torque drops as x2 for Primary Resistance starter, whereas line current reduces as x2 for Autotransformer starter!