Identify starter type from the diagram given below.
Automatic DOL Starter
Automatic Primary Resistance Starter
Automatic Auto-transformer Starter
Automatic Star-Delta Starter
Automatic DOL Starter
A Direct-On-Line (DOL) starter connects a 3-phase induction motor directly across the full supply voltage, applying full line voltage to the motor terminals at startup. The automatic type incorporates contactors, a holding coil (No-Volt Coil or NVC), thermal overload relays (OLR), and push buttons (Start/Stop) to enable automated control and essential safety protections.
A Direct-On-Line (DOL) starter connects a 3-phase induction motor directly across the full supply voltage, applying full line voltage to the motor terminals at startup. The automatic type incorporates contactors, a holding coil (No-Volt Coil or NVC), thermal overload relays (OLR), and push buttons (Start/Stop) to enable automated control and essential safety protections.
IstтАЛ=IscтАЛ=5┬аto┬а7├ЧIflтАЛ тАФ starting current is full short-circuit current
TstтАЛ=TflтАЛ├Ч(IflтАЛIstтАЛтАЛ)2├ЧsflтАЛ тАФ starting torque in terms of full-load torque
When the green 'Start' push button is pressed, the control circuit completes, energizing the main contactor coil (NVC). The coil pulls in the main power contacts connecting the motor to the 3-phase supply while simultaneously closing an auxiliary contact (holding contact) in parallel with the Start button to keep the coil energized after release. If an overload occurs, the thermal overload relay (OLR) contacts open, de-energizing the main contactor coil and safely disconnecting the motor from the supply.
Provides maximum starting torque (TstтАЛ) equal to full-voltage starting torque.
Draws very high starting current (5 to 7 times the full-load current).
Contains fundamental protection against overloads (via OLR) and undervoltage/supply failure (via No-Volt Coil).
Simple, compact, and highly economical design.
Provides 100% starting torque at startup.
Easy to install, operate, and maintain.
High starting current causes significant voltage dips in the power supply line.
High thermal and mechanical stress on motor windings during starting.
Not suitable for heavy or high-rating motors due to supply line disturbance.
Small 3-phase squirrel cage induction motors typically rated up to 5 HP (3.7 kW).
Water pumps, small machine tools, fans, and blowers.
Option B (Automatic Primary Resistance Starter) uses resistors in series with stator lines to reduce starting voltage and current.
Option C (Automatic Auto-transformer Starter) uses tapped autotransformers to step down starting voltage for higher rating motors (> 20 HP).
Option D (Automatic Star-Delta Starter) connects motor windings initially in Star during startup and switches to Delta during running, reducing starting current to 1/3.
A is correct тАФ The given schematic depicts an Automatic Direct-On-Line (DOL) starter featuring a main contactor, thermal overload relay, and Start/Stop push-button control circuit.
Always remember that in a DOL starter, IstтАЛ=IscтАЛ, which causes starting torque TstтАЛтИЭV2. In contrast, for Star-Delta starters, both starting current and starting torque are reduced to 31тАЛ of their DOL values.