If a 500 MVA, 11 kV three-phase generator at 50 Hz feeds, through a transfer impedance of (0.0 +j0.605) ╬й/phase, an infinite bus also at 11 kV, then the maximum steady state power transfer on the base of 500 MVA and 11 kV is
0 pu
0.8 pu
0.5 pu
0.4 pu
0.4 pu
D is correct because the per-unit impedance calculation yields 2.5pu, resulting in a maximum power transfer of 0.4pu.
Rating S = 500 MVA, Voltage V = 11 kV, Frequency f = 50 Hz, Impedance X = j0.605 ╬й/phase.
PmaxтАЛ=XpuтАЛтИгVтИгтИгEтИгтАЛ and XpuтАЛ=XohmтАЛ├Ч(VbaseтАЛ)2SbaseтАЛтАЛ
Calculate Base Impedance
First, find the base impedance of the system using the given rating and voltage: ZbaseтАЛ=SbaseтАЛ(VbaseтАЛ)2тАЛ.
ZbaseтАЛ=500├Ч106(11├Ч103)2тАЛ=500├Ч106121├Ч106тАЛ=0.242╬й
Calculate Per-Unit Impedance
Convert the physical impedance to per-unit value: XpuтАЛ=ZbaseтАЛXohmтАЛтАЛ.
XpuтАЛ=0.2420.605тАЛ=2.5pu
Calculate Maximum Power Transfer
For an infinite bus and a generator, assuming тИгVтИг=тИгEтИг=1.0 pu, the steady state power limit is PmaxтАЛ=XpuтАЛтИгVтИгтИгEтИгтАЛ.
PmaxтАЛ=2.51.0├Ч1.0тАЛ=0.4pu
D is correct because the per-unit impedance calculation yields 2.5pu, resulting in a maximum power transfer of 0.4pu.
This concept is fundamental to the 'Swing Equation' and 'Equal Area Criterion' topics in power system stability analysis.