The reactance of a generator designated X" is given as 0.25 pu based on the generatorтАЩs name plate rating of 18 kV, 500 MVA. If the base for calculations is changed to 20 kV, 100 MVA, the generator reactance X" on new base will be
0.25 pu
0.05 pu
0.0405 pu
0.25 pu
0.0405 pu
The per-unit reactance of a machine varies depending on the chosen base power and base voltage. To convert from an old base to a new base, the impedance must be scaled by the ratio of the new and old base MVA and the inverse square of the ratio of the new and old base voltages.
The per-unit reactance of a machine varies depending on the chosen base power and base voltage. To convert from an old base to a new base, the impedance must be scaled by the ratio of the new and old base MVA and the inverse square of the ratio of the new and old base voltages.
Xpu,newтАЛ=Xpu,oldтАЛ├Ч(Sbase,oldтАЛSbase,newтАЛтАЛ)├Ч(Vbase,newтАЛVbase,oldтАЛтАЛ)2 тАФ Per-unit impedance base change formula
The per-unit impedance ZpuтАЛ is proportional to Vbase2тАЛZactualтАЛ├ЧSbaseтАЛтАЛ. When shifting to a new base (SnewтАЛ,VnewтАЛ) from an old base (SoldтАЛ,VoldтАЛ), the relationship is derived as XnewтАЛ=XoldтАЛ├Ч(SoldтАЛSnewтАЛтАЛ)├Ч(VnewтАЛVoldтАЛтАЛ)2. Substituting the given values: 0.25├Ч(500100тАЛ)├Ч(2018тАЛ)2=0.25├Ч0.2imes0.81=0.0405 pu.
Per-unit values are dimensionless and depend on the selection of base quantities.
The square of the voltage ratio is inversely proportional because ZbaseтАЛ=SbaseтАЛVbase2тАЛтАЛ.
Base change is essential in power system analysis when components have different rating bases.
Simplifies power system calculations by removing transformer turns ratios.
Allows direct comparison of equipment with different ratings.
Requires careful selection of consistent bases across the entire system.
Errors in base selection lead to systemic miscalculations in fault analysis.
Short circuit analysis
Load flow studies
Stability analysis of power systems
The voltage ratio is 18/20, which is 0.9. Its square is 0.81.
The MVA ratio is 100/500, which is 0.2.
Option A and D are identical and incorrect as they do not account for the base change.
C is correct тАФ The per-unit reactance is calculated as 0.0405 pu after scaling by the MVA ratio (0.2) and the square of the voltage ratio (0.81).
Always remember that the voltage ratio is squared, while the MVA ratio is linear; this is a common point of error in competitive exams.