The reactance of a generator designated X" is given as 0.25 pu based on the generatorās name plate rating of 18 kV, 500 MVA. If the base for calculations is changed to 20 kV, 100 MVA, the generator reactance X" on new base will be
025 pu
0.05 pu
0.0405 pu
0.25 pu
025 pu
Quick Summary: Practice and solve "The reactance of a generator designated X" is given as 0.25 pu based on the generatorās name plate r..." for Electrical - Power System. The correct answer is Option A: 025 pu. Detailed step-by-step solution, conceptual clarity, and formulas on Examoogle.
Answer:
Option **(c) **