Examoogle
ExamsTest SeriesCBATRank CheckPrevious Year PapersPassBook StoreMy BooksAI Tutor
ЁЯЫТ0
рдЕA
Examoogle

India's most trusted platform for competitive exam PDF books. Expert-authored, watermark-protected, instant access.

Exams & Practice
All Exams & SyllabusMock Test SeriesPrevious Year PapersPractice Questions (MCQs)Recruitment Notifications
Quick Links
Examoogle AI TutorExam NewsBook StoreMy BooksLogin / Sign Up
Support
About UsRefund PolicyPrivacy PolicyTerms of UseContact Us
┬й 2026 Examoogle. India's #1 competitive exam AI tutor.
ЁЯФТ SSL SecuredЁЯУ▒ UPI AcceptedЁЯз╛ GST Invoice
Examoogle

Join 60,000+ competitive exam aspirants

or with email
By continuing, you agree to ourTerms of Service&Privacy Policy
Your Cart
SubtotalтВ╣0
TotalтВ╣0
Examoogle тАв User тАв info@examoogle.com тАв EE-2024-8821
Chapter 1 of 12 тАв Page 1 of 248ЁЯФТ Protected PDF тАв Watermarked
Back to Practice Questions
ElectricalPower System
PrevNext

If fault current is 30A and peak up current is 7.5A then PSM is

A

4

B

5

C

6

D

5

Correct Answer

тЪЩя╕П TE тАв Technical Direct FormulaElectricalPower System
Option A

4

Quick Summary:

Given: Fault current IfI_{f}IfтАЛ = 30A, Pickup current IpI_{p}IpтАЛ = 7.5A

ЁЯУРMAMath SolutionDirect Formula
ЁЯУЛ Given

Fault current IfI_{f}IfтАЛ = 30A, Pickup current IpI_{p}IpтАЛ = 7.5A

ЁЯФв Formula Used

PSM=IfIpPSM = \frac{I_f}{I_p}PSM=IpтАЛIfтАЛтАЛ

ЁЯФв Step-by-Step Solution
1

Identify given parameters

Identify the primary parameters required for Plug Setting Multiplier (PSM) calculation: the fault current If=30AI_f = 30AIfтАЛ=30A and the relay pickup current Ip=7.5AI_p = 7.5AIpтАЛ=7.5A.

If=30A,Ip=7.5AI_f = 30A, I_p = 7.5AIfтАЛ=30A,IpтАЛ=7.5A

2

Apply PSM formula

The Plug Setting Multiplier is defined as the ratio of fault current flowing in the relay coil to the pickup current.

PSM=IfIpPSM = \frac{I_f}{I_p}PSM=IpтАЛIfтАЛтАЛ

3

Calculate the result

Substitute the given values into the formula: PSM=30/7.5=4PSM = 30 / 7.5 = 4PSM=30/7.5=4.

PSM=307.5=4PSM = \frac{30}{7.5} = 4PSM=7.530тАЛ=4

тЬЕ

A is correct because the ratio of the fault current to the pickup current results in a PSM of 4.

Core Concepts Used
Click any tag to open in AI Tutor
Relay Protection Plug Setting Multiplier Fault Analysis
ЁЯТб EXAM TIP

PSM is a critical factor in determining the operating time of an IDMT relay; higher PSM values lead to faster operation times according to the inverse characteristic curve.

Related Questions

ElectricalPower System
The specified quantities of Generation bus is
ElectricalPower System
When an alternator connected to the bus-bar is shut down the bus-bar voltage will
ElectricalPower System
The current drawn by the line due to corona losses is _______
ElectricalPower System
The specified quantities of load bus are
ElectricalPower System
The advantages of high transmission voltage are ______

Discussion (0)

Loading discussion...
PrevNext