Examoogle
ExamsTest SeriesRank CheckPrevious Year PapersPassBook StoreMy BooksAI Tutor
🛒0
अA
Examoogle

India's most trusted platform for competitive exam PDF books. Expert-authored, watermark-protected, instant access.

Exams & Practice
All Exams & SyllabusMock Test SeriesPrevious Year PapersPractice Questions (MCQs)Recruitment Notifications
Quick Links
Examoogle AI TutorExam NewsBook StoreMy BooksLogin / Sign Up
Support
About UsRefund PolicyPrivacy PolicyTerms of UseContact Us
© 2026 Examoogle. India's #1 competitive exam AI tutor.
🔒 SSL Secured📱 UPI Accepted🧾 GST Invoice
Examoogle

Join 60,000+ competitive exam aspirants

or with email
By continuing, you agree to ourTerms of Service&Privacy Policy
Your Cart
Subtotal₹0
Total₹0
Examoogle • User • info@examoogle.com • EE-2024-8821
Chapter 1 of 12 • Page 1 of 248🔒 Protected PDF • Watermarked
Back to Practice Questions
ElectricalPower System
PrevNext

If PSM is 5 and peak up current is 7A then fault current is

A

30A

B

35A

C

5A

D

5A

Correct Answer

Direct FormulaElectricalPower System
Option B

35A

Quick Summary: Given: Plug Setting Multiplier (PSM) = 5, Pickup Current (I_pickup) = 7A

📋 Given

Plug Setting Multiplier (PSM) = 5, Pickup Current (IpickupI_{pickup}Ipickup​) = 7A

🔢 Formula Used

PSM=FaultCurrent(If)PlugSetting(Ip)PSM = \frac{Fault Current (I_f)}{Plug Setting (I_p)}PSM=PlugSetting(Ip​)FaultCurrent(If​)​

🔢 Step-by-Step Solution
1

Define the relationship

The Plug Setting Multiplier (PSM) is defined as the ratio of the actual fault current to the pickup current (or plug setting).

PSM=IfIpPSM = \frac{I_f}{I_p}PSM=Ip​If​​

2

Rearrange the formula

To find the fault current IfI_fIf​, rearrange the formula as If=PSM×IpI_f = PSM \times I_pIf​=PSM×Ip​.

If=PSM×IpI_f = PSM \times I_pIf​=PSM×Ip​

3

Calculate the fault current

Substitute the given values PSM=5PSM = 5PSM=5 and Ip=7AI_p = 7AIp​=7A into the equation.

If=5×7=35AI_f = 5 \times 7 = 35AIf​=5×7=35A

✅

B is correct because multiplying the Plug Setting Multiplier of 5 by the pickup current of 7A results in a fault current of 35A.

Core Concepts Used
Click any tag to open in AI Tutor
Relay Protection Plug Setting Multiplier Fault Current Calculation
💡 EXAM TIP

The PSM is a critical parameter in Inverse Definite Minimum Time (IDMT) relay coordination, directly determining the operating time of the relay on the time-current characteristic curve.

Related Questions

ElectricalPower System
The specified quantities of Generation bus is
ElectricalPower System
When an alternator connected to the bus-bar is shut down the bus-bar voltage will
ElectricalPower System
The current drawn by the line due to corona losses is _______
ElectricalPower System
The specified quantities of load bus are
ElectricalPower System
The advantages of high transmission voltage are ______

Discussion (0)

Loading discussion...
PrevNext