Join 60,000+ competitive exam aspirants
If the transformer winding resistances and reactances are expressed in pu value, then
R1(pu)=R2(pu) and X1(pu)=X2(pu)
R1(pu)=R2(pu) and X1(pu)=X2(pu)
R1(pu)=0.5R2(pu) and X1(pu)=0.5X2(pu)
R1(pu)=R2(pu) and X1(pu)=X2(pu)
R1(pu)=R2(pu) and X1(pu)=X2(pu)
Quick Summary: In a transformer, the per-unit (pu) values of impedance parameters like resistance and reactance are the same when referred to either the primary or secondary side. This is because per-unit normalization is specifically designed to eliminate the effect of the transformer's turns ratio $a$ by normalizing against the respective side's base values.
In a transformer, the per-unit (pu) values of impedance parameters like resistance and reactance are the same when referred to either the primary or secondary side. This is because per-unit normalization is specifically designed to eliminate the effect of the transformer's turns ratio a by normalizing against the respective side's base values.
Zpu=(kV)base2ZΩ×(MVA)base — Per-unit impedance calculation formula
R1(pu)=R2(pu) — Equality of pu resistance
X1(pu)=X2(pu) — Equality of pu reactance
The per-unit value is defined as the ratio of actual value to base value: Zpu=ZbaseZactual. When referring parameters from the secondary to the primary, the actual resistance R2 is multiplied by a2, and the base impedance Zbase,2 is also multiplied by a2 when referred to the primary base. Consequently, the factor a2 cancels out, leading to identical per-unit values regardless of the side of reference.
Per-unit system normalizes parameters to a common base.
The turns ratio a does not affect per-unit values.
This simplifies multi-winding transformer analysis in power systems.
Calculations become independent of voltage levels.
Eliminates the need for turns ratio calculations.
Simplifies power system network analysis.
Values of machines are typically within a narrow range regardless of rating.
Requires careful selection of consistent base values.
Does not account for inherent saturation in high-precision modeling.
Short circuit studies.
Power flow analysis in multi-bus systems.
Transformer impedance matching.
The per-unit system is the industry standard for analyzing interconnected power systems consisting of various transformers and transmission lines.
Option A, B, and C are incorrect because they imply dependence on the side of reference, which contradicts the fundamental property of the per-unit system.
D is correct — The per-unit impedance (resistance and reactance) of a transformer is a constant value independent of whether it is referred to the primary or secondary side.
Always convert actual ohms to per-unit values before performing fault calculations; it reduces algebraic complexity significantly and prevents errors involving the transformer turns ratio.