In a loop test performed for localizing the earth fault in cable, fault resistance
Affects the balance condition
Affects the sensitivity of bridge
Affect the value of cable resistance
All of above
Affects the sensitivity of bridge
In a Murray loop test used for fault localization, the fault resistance is connected in series with the galvanometer branch of the Wheatstone bridge. Because the galvanometer sensitivity is inversely proportional to the resistance in its circuit, a high fault resistance significantly reduces the current through the galvanometer, thereby reducing the sensitivity of the bridge balance detection.
In a Murray loop test used for fault localization, the fault resistance is connected in series with the galvanometer branch of the Wheatstone bridge. Because the galvanometer sensitivity is inversely proportional to the resistance in its circuit, a high fault resistance significantly reduces the current through the galvanometer, thereby reducing the sensitivity of the bridge balance detection.
SgтАЛ=╬ФRIgтАЛтАЛ тАФ Galvanometer sensitivity as a function of deflection current
IgтАЛтЙИRbridgeтАЛ+RfтАЛEтАЛ тАФ Galvanometer current dependence on fault resistance
The Murray loop test employs a bridge circuit where the fault path resistance acts as part of the galvanometer loop. When the bridge is near balance, the potential difference across the galvanometer is minimized. If the fault resistance (RfтАЛ) is high, it limits the deflection current IgтАЛ produced by even a small bridge unbalance, making it difficult for the operator to determine the null point accurately.
Murray loop test is essentially a Wheatstone bridge configuration.
The fault resistance RfтАЛ does not shift the balance point in a bridge circuit, it only degrades detection precision.
High impedance faults make the bridge 'sluggish' or insensitive to small adjustments in the ratio arms.
A sensitive galvanometer or external amplifier is often needed for high-resistance earth faults.
Simple circuit configuration for locating low-resistance ground faults.
Independent of the lead wire resistance if a return conductor is used.
Performance degrades significantly with high fault resistance.
Requires access to both ends of the cable for better accuracy in some variations (Varley loop).
Underground power cable maintenance.
Telecommunication cable fault localization.
Option A is incorrect because the balance condition depends on the ratio of the arms, which is independent of the absolute value of RfтАЛ in the galvanometer branch.
Option C is incorrect because RfтАЛ is an external fault parameter, not a property of the cable's inherent characteristic resistance.
B is correct тАФ High fault resistance increases the total impedance of the galvanometer branch, which drastically reduces the sensitivity of the bridge to detection of the balance point.
Always remember that in bridge-based measurements, any resistance added to the galvanometer path acts as a series damper, reducing the deflection per unit change of the arm resistance.