In a suspension type insulator potential difference is
Maximum across the lowest disc
Maximum across top most disc
Uniformly distributed over the disc
None of the above
Maximum across the lowest disc
In a string of suspension insulators, the voltage is not distributed equally across all discs due to the presence of shunt capacitance between each metal link and the ground tower structure. This unequal distribution results in the lowest disc, which is closest to the energized conductor, experiencing the maximum potential stress.
In a string of suspension insulators, the voltage is not distributed equally across all discs due to the presence of shunt capacitance between each metal link and the ground tower structure. This unequal distribution results in the lowest disc, which is closest to the energized conductor, experiencing the maximum potential stress.
VnтАЛ=VnтИТ1тАЛ+InтАЛXcтАЛ тАФ Voltage across nth disc
╬╖=n├ЧVoltageacrosslowestdiscTotalVoltageтАЛ├Ч100 тАФ String efficiency
The metal cross-arm of the transmission tower acts as a ground plane. Because of the mutual capacitance (CmтАЛ) between discs and shunt capacitance (CsтАЛ) to the tower, leakage currents flow to the ground from each junction point. Since the charging current is additive towards the conductor, the voltage drop across the bottom-most insulator disc is highest.
The unequal potential distribution is caused by shunt capacitance to the tower.
String efficiency is always less than 100% for suspension insulators.
Grading of insulators (using different capacitance values) can equalize voltage distribution.
Increasing the cross-arm length reduces shunt capacitance, improving efficiency.
High mechanical strength
Easy to replace damaged units
Flexible design for various voltage levels
Non-uniform voltage distribution
Higher cost compared to pin type insulators
High voltage overhead transmission lines (> 33 kV)
Substations and distribution switching yards
To achieve a more uniform distribution, guard rings or grading rings are often employed.
Option B is incorrect as the top-most disc has the lowest potential stress.
A is correct тАФ The potential gradient is highest across the disc nearest to the conductor due to the cumulative charging currents caused by shunt capacitances.
Always remember that for any string of insulators, the unit closest to the line conductor is most stressed; guard rings are the standard solution used to mitigate this.