In case of a 3-phase short circuit in a system, the power fed into the system is
Mostly reactive
Mostly active
Active and reactive both equal
Reactive only
Mostly reactive
In a 3-phase short circuit fault, the system impedance becomes predominantly inductive because the fault current is limited primarily by the leakage reactances of transformers, generators, and transmission lines. Since the resistance of these components is negligible compared to their inductive reactance, the power supplied to the fault point is almost entirely reactive.
In a 3-phase short circuit fault, the system impedance becomes predominantly inductive because the fault current is limited primarily by the leakage reactances of transformers, generators, and transmission lines. Since the resistance of these components is negligible compared to their inductive reactance, the power supplied to the fault point is almost entirely reactive.
Q=I2X тАФ reactive power absorbed by inductive reactance under fault conditions
P=VIcos╧ХтЙИ0 тАФ active power flow during a dead short circuit
During a symmetrical fault, the voltage at the fault location drops to zero. The current flows from the source through the system's inductive components to the fault point. Because the phase angle difference between the voltage and the high magnitude current approaches 90 degrees (lagging), the real power component (P=VIcos╧Х) tends toward zero, while the reactive power component (Q=VIsin╧Х) dominates.
Short circuit faults are inductive in nature due to high leakage reactance.
The power factor during a bolted 3-phase fault is nearly zero lagging.
Resistance of system components (transformers/cables) is very low compared to reactance.
The fault current IfтАЛ lags the source voltage by nearly 90┬░.
Protective relay setting coordination
Short circuit MVA capacity calculation
In practice, the resistance is not zero, so a small amount of active power is consumed as I2R losses, but it is insignificant compared to the reactive power associated with the magnetic fields.
Option B is incorrect because active power requires a resistive load component which is minimal in high-voltage transmission and generation systems.
A is correct тАФ The fault path is highly inductive, causing the current to lag the voltage by nearly 90 degrees, resulting in mostly reactive power flow.
Always remember that in power systems, components like transformers and long lines are inductive; therefore, during any fault, the system essentially behaves as a pure inductor.