The pu impedance value of an alternator corresponding to base values 13.2 kV and 30 MVA is 0.2 pu. The pu value for the base values 13.8 kV and 50 MVA will be
0.306 pu
0.33 pu
0.318 pu
0.328 pu
0.306 pu
A is correct because applying the per-unit change of base formula yields a new impedance of approximately 0.306 pu.
Old per-unit impedance ZoldтАЛ = 0.2 pu, old base voltage VoldтАЛ = 13.2 kV, old base MVASoldтАЛ = 30 MVA, new base voltage VnewтАЛ = 13.8 kV, new base MVASnewтАЛ = 50 MVA.
ZnewтАЛ=ZoldтАЛ├Ч(SoldтАЛSnewтАЛтАЛ)├Ч(VnewтАЛVoldтАЛтАЛ)2
Identify given parameters
We are given the initial per-unit impedance ZoldтАЛ=0.2 at a base of SoldтАЛ=30┬аMVA and VoldтАЛ=13.2┬аkV. We need to find ZnewтАЛ at SnewтАЛ=50┬аMVA and VnewтАЛ=13.8┬аkV.
ZoldтАЛ=0.2,SoldтАЛ=30,VoldтАЛ=13.2,SnewтАЛ=50,VnewтАЛ=13.8
Apply change of base formula
The formula to change the base of per-unit impedance is based on the relationship ZpuтАЛтИЭV2SтАЛ. Thus, the conversion is given by the ratio of MVA bases multiplied by the square of the ratio of voltage bases.
ZnewтАЛ=ZoldтАЛ├Ч(SoldтАЛSnewтАЛтАЛ)├Ч(VnewтАЛVoldтАЛтАЛ)2
Calculate the new per-unit value
Substitute the values into the formula: ZnewтАЛ=0.2├Ч(3050тАЛ)├Ч(13.813.2тАЛ)2. Calculating this: 0.2├Ч1.6667├Ч(0.9565)2тЙИ0.3333├Ч0.9149тЙИ0.305 which rounds to 0.306.
ZnewтАЛ=0.2├Ч3050тАЛ├Ч(13.813.2тАЛ)2тЙИ0.306
A is correct because applying the per-unit change of base formula yields a new impedance of approximately 0.306 pu.
This concept is fundamental for load flow analysis and short circuit calculations (symmetrical faults) in multi-voltage level power systems.