No load compensation of a high voltage line involves
Shunt capacitors
Shunt reactors
Series capacitors
Series reactors
Shunt reactors
No load compensation in high voltage (HV) transmission lines is required to mitigate the Ferranti effect, which causes the receiving end voltage to rise significantly above the sending end voltage at light loads or no-load conditions. Shunt reactors are connected in parallel to the line to absorb the excess reactive power generated by the line capacitance, thereby maintaining voltage stability.
No load compensation in high voltage (HV) transmission lines is required to mitigate the Ferranti effect, which causes the receiving end voltage to rise significantly above the sending end voltage at light loads or no-load conditions. Shunt reactors are connected in parallel to the line to absorb the excess reactive power generated by the line capacitance, thereby maintaining voltage stability.
QcompтАЛ=V2тЛЕ╧ЙC
VreceivingтАЛ=VsendingтАЛтЛЕsec(╬▓l)
Transmission lines possess inherent shunt capacitance per unit length. At no load, the charging current ICтАЛ=VтЛЕ╧ЙC flows through the line inductance. This reactive power interaction leads to a voltage rise at the receiving end. Shunt reactors provide an inductive reactive power QLтАЛ=XLтАЛV2тАЛ which compensates for the capacitive reactive power QCтАЛ=V2тЛЕ╧ЙC, effectively neutralizing the charging current and keeping the voltage profile flat.
Used to neutralize the Ferranti effect in EHV/UHV lines.
Installed at the receiving end or along the length of long lines.
Shunt reactors provide lagging VARs to compensate for leading VARs generated by line capacitance.
Essential for lines typically longer than 200 km.
Prevents dangerous overvoltages at receiving end during low load.
Reduces insulation stress on equipment.
Improves voltage regulation.
Increases capital cost of transmission system.
May require switching arrangements to disconnect reactors during peak load.
Extra High Voltage (EHV) overhead transmission lines.
Underground power cables where capacitance is very high.
The Ferranti effect is more pronounced in long lines due to the product of series resistance and shunt capacitance.
Option A (Shunt capacitors) are used to improve power factor and voltage in distribution systems, which would worsen the Ferranti effect in HV lines.
B is correct тАФ Shunt reactors are used to absorb capacitive reactive power and control the voltage rise due to the Ferranti effect.
Always remember: Shunt capacitors are for low voltage/inductive loads (boost voltage), while shunt reactors are for high voltage/capacitive effects (lower voltage).