Join 60,000+ competitive exam aspirants
For a good voltage profile under no load condition, a long line needs
Shunt capacitors at receiving end
Shunt reactor at receiving end
Shunt resistance at receiving end
Shunt capacitor at mid-point
Shunt reactor at receiving end
Long transmission lines exhibit the Ferranti effect, where the receiving end voltage exceeds the sending end voltage at no-load or light-load conditions due to line capacitance. To counter this voltage rise, inductive compensation in the form of a shunt reactor is connected at the receiving end to absorb the excess reactive power.
Long transmission lines exhibit the Ferranti effect, where the receiving end voltage exceeds the sending end voltage at no-load or light-load conditions due to line capacitance. To counter this voltage rise, inductive compensation in the form of a shunt reactor is connected at the receiving end to absorb the excess reactive power.
VrтАЛ=VsтАЛcosh(╬│l) тАФ No-load receiving end voltage for a long transmission line
QcompтАЛ=V2╧ЙCshuntтАЛ тАФ Reactive power compensation required
At no load, the shunt capacitance (C) of the long line draws a leading capacitive current from the source. This current flows through the series inductance (L) and resistance (R) of the line, creating a voltage drop that results in a leading phase shift, effectively boosting the voltage at the receiving end. A shunt reactor provides an inductive current (ILтАЛ) that cancels the capacitive current (ICтАЛ), neutralizing the reactive power and stabilizing the voltage profile.
Ferranti effect is predominant in long transmission lines (length > 250 km).
It occurs because IchargingтАЛ flows through the line reactance.
Shunt reactors provide lagging VARs to consume leading VARs generated by line shunt capacitance.
The effect is proportional to the square of the line length.
Maintains voltage within permissible limits at no-load.
Prevents insulation stress on receiving end equipment.
Reduces overvoltage risks during switching transients.
Adds cost and space requirements at the substation.
Requires maintenance of additional inductive hardware.
May impact power factor during high-load conditions if not switched off.
Extra High Voltage (EHV) and Ultra High Voltage (UHV) transmission networks.
Long distance power corridors where load fluctuation is extreme.
Shunt capacitors (Option A) are used to improve power factor by providing lagging VARs, which would worsen the Ferranti effect.
The shunt reactor is essentially an inductor connected in shunt across the line and neutral.
B is correct тАФ Shunt reactors are used at the receiving end of a long line to neutralize the capacitive charging current and suppress the voltage rise caused by the Ferranti effect.
Always remember: Capacitors are for 'lagging' loads (improve PF), while Reactors are for 'leading' capacitive effects (Ferranti effect correction).