Inductance of single phase two wire line is
4×10−7ln(DsDm) H/m
0.4×10−7ln(DsDm) H/m
4×10−7ln(DmDs) H/m
0.4×10−7ln(DmDs) H/m
4×10−7ln(DsDm) H/m
The loop inductance of a single-phase two-wire transmission line is derived by considering the flux linkages of both conductors. The total inductance is given by L=4×10−7ln(DsDm) H/m, where Dm is the distance between conductor centers and Ds is the geometric mean radius (GMR).
The loop inductance of a single-phase two-wire transmission line is derived by considering the flux linkages of both conductors. The total inductance is given by L=4×10−7ln(DsDm) H/m, where Dm is the distance between conductor centers and Ds is the geometric mean radius (GMR).
L=2×10−7ln(DsDm) H/m per conductor
Lloop=4×10−7ln(DsDm) H/m
The total inductance per unit length is the sum of the inductances of the two conductors. Since the current flows out through one wire and returns through the other, their flux linkages add up. The internal flux linkage contributes 0.5×10−7 H/m per conductor, and the external flux linkage is calculated based on the distance between wires relative to the radius of the conductors.
Inductance accounts for both internal and external flux linkages.
For solid round conductors, Ds=r×e−0.25=0.7788r.
Inductance increases with the spacing Dm between conductors.
Inductance decreases as the radius of the conductor increases (due to larger Ds).
Design of single-phase power distribution lines.
Analysis of transmission line voltage drop and power factor.
Option B and D are incorrect because 0.4×10−7 is not the standard constant for the loop inductance calculation.
Option C is incorrect because the ratio must be DsDm to ensure a positive value for natural log, as Dm>Ds.
A is correct — the loop inductance of a single-phase two-wire line is given by 4×10−7ln(DsDm) H/m.
Remember that loop inductance is exactly twice the inductance of a single conductor; always check if the question asks for 'per conductor' or 'per loop'.