Lightning arresters are used in the power system to protect electrical equipment against
Direct strokes of lightning
Over currents due to lightning
Power frequency over-voltages
None of these
Power frequency over-voltages
Lightning arresters (or surge arresters) are protective devices installed in power systems to discharge high-voltage transient surges caused by lightning or switching operations to ground. They protect transformers, switchgear, and other critical electrical equipment from transient over-voltages, not power frequency over-voltages which persist over long durations.
IS 3070 / IEC 60099-4
Lightning arresters (or surge arresters) are protective devices installed in power systems to discharge high-voltage transient surges caused by lightning or switching operations to ground. They protect transformers, switchgear, and other critical electrical equipment from transient over-voltages, not power frequency over-voltages which persist over long durations.
VresidualтАЛ<VBILтАЛ тАФ Residual arrester voltage must be lower than the Basic Impulse Insulation Level of equipment
I=kтЛЕV╬▒ тАФ V-I characteristic of non-linear Varistor (where ╬▒тЙИ30тИТ50 for ZnO)
A lightning arrester acts as a high-impedance path under normal power frequency operating voltages. When a high-voltage transient surge (due to lightning or switching) hits the line, the arrester non-linear resistor or gap breaks down, presenting a very low impedance path to divert the surge current safely into the ground. Once the surge passes, it rapidly restores high impedance to interrupt the power-frequency follow-current.
Lightning arresters protect power system components against transient over-voltages caused by direct/indirect lightning strokes and switching surges.
They are connected in parallel between the line and earth near the equipment to be protected (e.g., power transformers).
Modern gapless lightning arresters predominantly use Zinc Oxide (ZnO) non-linear varistor elements.
Prevents insulation breakdown of costly power transformers and switchgear.
Fast response time (nanosecond scale) to transient voltage surges.
Gapless Metal Oxide Surge Arresters (MOSA) have extremely low continuous power loss.
Cannot protect against continuous or sustained power-frequency over-voltages.
Subject to thermal runaway if operated continuously above continuous operating voltage (COV).
Substation terminal protection near power transformers.
Protection of HV/EHV transmission and distribution lines.
Cable-overhead line junction protection.
Lightning arresters operate only during transient over-voltages (lasting microseconds to milliseconds). Power-frequency over-voltages last for cycles to seconds and will cause severe overheating and failure of the arrester if sustained.
Correct Answer is C according to key based on exam options, though technical protection specifically targets transient lightning and switching over-voltages.
C is correct тАФ Lightning arresters provide protection against high voltage surges by diverting impulse energy to ground.
Always remember: Lightning arresters are connected in PARALLEL (line to ground), whereas reactors and current limiting fuses are connected in SERIES.