Join 60,000+ competitive exam aspirants
Normally Supply voltage is applied on ___________ side during Short Circuit test on the transformer.
LV
HV
both side (one by one)
None of these
HV
Quick Summary: In the Short Circuit (SC) test, the low-voltage (LV) winding is short-circuited, and a reduced voltage is applied to the high-voltage (HV) winding to circulate the full-load rated current. Applying voltage to the HV side is preferred because it requires a more manageable, lower value of current for the same power rating of the supply equipment.
In the Short Circuit (SC) test, the low-voltage (LV) winding is short-circuited, and a reduced voltage is applied to the high-voltage (HV) winding to circulate the full-load rated current. Applying voltage to the HV side is preferred because it requires a more manageable, lower value of current for the same power rating of the supply equipment.
Psc=Irated2⋅Req — Copper loss calculated from SC test
Zeq=IscVsc — Equivalent impedance referred to HV side
The SC test is conducted to determine the full-load copper losses and equivalent impedance parameters (Req, Xeq) of the transformer. By shorting the LV side, the core flux becomes very small (since Vapplied≈0.05 to 0.1 of rated voltage), meaning core losses are negligible and the total power measured by the wattmeter represents almost entirely copper losses.
LV winding is always short-circuited to avoid extremely high currents during testing.
The applied voltage is typically 5-10% of the rated voltage.
Wattmeter reading at SC test is treated as Full Load Copper Loss.
Core losses are neglected due to low flux density at reduced applied voltage.
Requires low power source capacity.
Accurately measures transformer leakage impedance.
Does not determine core losses.
Requires precise measurement of low voltage levels.
Calculation of efficiency at any load.
Determining voltage regulation of the transformer.
The test is performed on the HV side because the rated current IHV=VHVS is smaller than ILV, making it easier to control with standard laboratory equipment.
If the test were performed on the LV side, the supply source would need to provide a very high current at a very low voltage, which is practically difficult.
B is correct — The HV side is used for applying voltage during a short-circuit test to allow for lower current handling and higher measurement accuracy.
Always remember: SC test measures Copper loss (variable loss) and OC test measures Iron loss (constant loss).