Power factor can be improved by using
Static capacitors
Synchronous condenser
Phase advancer
All of above
All of above
Power factor improvement is achieved by neutralizing the lagging reactive power (inductive component) of the load. This is done by supplying leading reactive power using devices like capacitors or over-excited synchronous motors, thereby reducing the total current drawn from the source for the same real power delivery.
Power factor improvement is achieved by neutralizing the lagging reactive power (inductive component) of the load. This is done by supplying leading reactive power using devices like capacitors or over-excited synchronous motors, thereby reducing the total current drawn from the source for the same real power delivery.
P=VIcos╧Х тАФ Relation between real power and power factor
Q=VIsin╧Х тАФ Reactive power component
QrequiredтАЛ=P(tan╧Х1тАЛтИТtan╧Х2тАЛ) тАФ Reactive power to be compensated
The principle relies on the Power Triangle, where total apparent power S=P+jQ. By introducing a leading reactive power source (QcapтАЛ), the net reactive power QnetтАЛ=QLтАЛтИТQcapтАЛ is reduced, effectively decreasing the phase angle ╧Х between voltage and current, thus increasing cos╧Х.
A lagging power factor is typically caused by inductive loads like induction motors and transformers.
Static capacitors provide fixed compensation for local loads.
Synchronous condensers are over-excited synchronous motors running at no-load to provide variable compensation.
Phase advancers are specifically used to improve the power factor of induction motors.
Reduced I2R losses in transmission and distribution lines.
Increased load-carrying capacity of existing electrical equipment.
Improved voltage regulation.
Reduction in electricity bills due to penalty avoidance.
High initial cost for large installations.
Synchronous condensers require additional maintenance due to rotating parts.
Static capacitors can lead to over-correction during low-load conditions.
Industrial plants with heavy motor loads.
Power transmission substations for voltage stability.
Large commercial buildings.
Standard power factor is generally kept between 0.9 and 0.95 lagging.
Static capacitors are the most common and economical method for low to medium voltage applications.
D is correct тАФ All listed devices (static capacitors, synchronous condensers, and phase advancers) are standard engineering methods used to improve power factor by supplying leading reactive power.
Always remember that power factor improvement only changes the reactive component; it does not alter the real power (P) requirement of the load.