Shunt compensation in in EHV line is used to improve
Stability and fault level
Fault level and voltage
Voltage profile and stability
Stability, fault level and voltage profile
Voltage profile and stability
Shunt compensation in EHV lines is primarily employed to maintain voltage levels along the line and enhance steady-state stability. By using shunt reactors or capacitors, the reactive power flow is balanced, preventing voltage swells during light loads and voltage drops during heavy loads.
Shunt compensation in EHV lines is primarily employed to maintain voltage levels along the line and enhance steady-state stability. By using shunt reactors or capacitors, the reactive power flow is balanced, preventing voltage swells during light loads and voltage drops during heavy loads.
VrecтАЛ=VsendтАЛcos(╬▓l)тИТIsendтАЛZcтАЛsin(╬▓l) тАФ Ferranti effect voltage at receiving end
P=XVSтАЛVRтАЛтАЛsin╬┤ тАФ Power transfer equation showing dependency on line reactance X
In EHV lines, the Ferranti effect causes voltage rise at the receiving end during light loads due to line capacitance. Shunt reactors absorb reactive power to mitigate this. Conversely, during heavy loads, shunt capacitors are used to supply reactive power, supporting the voltage profile and increasing the maximum power transfer capacity (PmaxтАЛ=XV1тАЛV2тАЛтАЛsin╬┤), thereby improving stability.
Shunt reactors are used to compensate for the charging current of long EHV lines.
Shunt capacitors are used to improve the voltage profile under heavy load conditions.
Stability is improved by reducing the effective transfer reactance of the line.
Fault level is primarily determined by source impedance and is not the primary function of shunt compensation.
Improved voltage regulation along the line length
Increased power transfer limit and steady-state stability
Reduction in Ferranti effect during low-load conditions
Requires complex control systems for SVC/STATCOM
Additional capital investment in power electronics or reactor banks
Long-distance EHV and UHV AC transmission lines
Industrial power systems with fluctuating inductive loads
Fault level is a property of the network topology and source impedance; shunt compensation adds reactive support but does not significantly change the short-circuit current availability.
Option D is incorrect because fault level is not a primary target for shunt compensation design.
C is correct тАФ Shunt compensation primarily regulates the voltage profile by controlling reactive power and enhances stability by reducing the effective reactance of the transmission line.
Always remember: Series compensation increases power transfer by reducing X, while shunt compensation maintains voltage levels by managing reactive power Q.