Shunt compensation in EHV line is used to
Improve stability
Reduce fault level
Improve voltage profile
Substitute for synchronous phase modifier
Improve voltage profile
Shunt compensation in EHV (Extra High Voltage) transmission lines is primarily employed to maintain voltage levels within permissible limits. It involves connecting reactive power compensation equipment (like shunt reactors or capacitors) in parallel with the transmission line to regulate voltage profile against variations in load.
Shunt compensation in EHV (Extra High Voltage) transmission lines is primarily employed to maintain voltage levels within permissible limits. It involves connecting reactive power compensation equipment (like shunt reactors or capacitors) in parallel with the transmission line to regulate voltage profile against variations in load.
QcompтАЛ=V2тЛЕBcompтАЛ тАФ Reactive power provided/absorbed by a shunt compensator with susceptance BcompтАЛ
VrтАЛ=VsтАЛтЛЕcos(╬▓l)тИТIsтАЛZcтАЛтЛЕsin(╬▓l) тАФ Basic voltage equation for transmission lines highlighting the effect of line parameters
EHV lines often experience the Ferranti effect under light load conditions due to their high shunt capacitance, leading to a voltage rise at the receiving end. Shunt reactors are used to absorb this reactive power, effectively lowering the voltage profile. Conversely, under heavy loads, shunt capacitors provide reactive power to boost the receiving-end voltage, ensuring the voltage remains close to nominal values.
Used to neutralize the effect of line shunt capacitance (Ferranti effect).
Essential in long EHV lines where charging current is significant.
Shunt reactors are typically installed at line ends or intermediate substations.
Does not inherently improve transient stability as effectively as series compensation.
Prevents voltage rise under light load conditions.
Reduces overvoltage stresses on equipment insulation.
Simple and cost-effective compared to active control methods.
Does not significantly improve steady-state power transfer capability.
Fixed shunt reactors may need to be disconnected at peak loads to avoid under-voltage.
Long distance EHV and UHV transmission lines.
Underground cable systems with high shunt capacitance.
Reactive power support at substation buses.
Option B (Reduce fault level) is typically achieved by using reactors in series or high impedance grounding, not shunt compensation.
Option D is incorrect because while shunt compensators perform similar voltage control tasks, the term 'substitute' is technically imprecise as synchronous condensers provide continuous reactive power control, unlike fixed shunt reactors.
C is correct тАФ Shunt compensation is primarily used to regulate the voltage profile by mitigating the reactive power imbalance in EHV lines.
Always remember: Shunt compensation deals with Voltage Profile regulation, while Series compensation is the primary method used to improve transient Power Stability by reducing effective line reactance.