Join 60,000+ competitive exam aspirants
Single core cables should have armour made of
Magnetic material
Nonmagnetic and non-conducting material
Nonmagnetic but conducting material
Conducting material
Nonmagnetic but conducting material
Single core cables carry alternating current which produces a time-varying magnetic field around the conductor. If a magnetic material were used for armouring, the alternating magnetic flux would induce eddy currents and hysteresis losses in the armour, leading to significant heating and power loss.
Single core cables carry alternating current which produces a time-varying magnetic field around the conductor. If a magnetic material were used for armouring, the alternating magnetic flux would induce eddy currents and hysteresis losses in the armour, leading to significant heating and power loss.
PlossтАЛ=I2RarmourтАЛ+PeddyтАЛ тАФ Power loss induced in armour
╬ж=тИлBтЛЕdA тАФ Magnetic flux linking the armour
The current I flowing through the conductor creates a magnetic field H according to Ampere's law. In single-core cables, the magnetic field is not cancelled out (unlike three-core cables where fields sum to zero). Using a magnetic material (like steel) as armour would cause it to act as a transformer core, inducing circulating eddy currents. By using a non-magnetic material (like aluminum), the relative permeability ╬╝rтАЛ is approximately 1, which prevents excessive inductive losses and overheating.
Magnetic material causes eddy current losses and hysteresis losses due to alternating flux.
Non-magnetic materials like aluminum or bronze are preferred to minimize losses.
Single core cables require specific attention to induced voltages in the armour.
Using non-magnetic armour reduces the inductive reactance of the cable system.
Minimizes eddy current losses
Reduces heat generation
Improves overall transmission efficiency
Non-magnetic materials are generally more expensive than steel
Reduced mechanical strength compared to steel armour
AC high-voltage single-core transmission
Submarine power cabling
For multi-core cables, the magnetic fields of the phases cancel each other, making magnetic armour (steel wire/tape) acceptable.
Option A is incorrect because it causes excessive heating and power loss in the armour due to induced EMFs.
C is correct тАФ Single core cables use nonmagnetic conducting armour to prevent inductive heating and power losses caused by alternating magnetic flux.
Always remember that in three-phase systems, magnetic armour is permissible for multi-core cables because the net magnetic field at any point outside the cable geometry is near zero.