Single core cables are usually not provided with armouring in order to
Avoid excessive loss in the armour
Make the cable more flexible
Make the cable non hygroscopic
None of above
Avoid excessive loss in the armour
Single core cables carry alternating current which produces a time-varying magnetic field around the conductor. If a magnetic armour (like steel wire or tape) is used, this field induces significant eddy currents and hysteresis losses in the armour, leading to overheating and reduced efficiency.
Single core cables carry alternating current which produces a time-varying magnetic field around the conductor. If a magnetic armour (like steel wire or tape) is used, this field induces significant eddy currents and hysteresis losses in the armour, leading to overheating and reduced efficiency.
PlossтАЛтИЭ╬ж2тЛЕf
IeddyтАЛ=dtтИТd╬жтАЛтЛЕR1тАЛ
According to Faraday's Law, the changing magnetic flux linked with the conductive armour material induces an Electromotive Force (EMF). Since the armour forms a closed loop or path, this EMF drives eddy currents IeтАЛ that cause ohmic heating (P=Ie2тАЛR). To mitigate these heavy power losses, single core AC cables use non-magnetic armouring (like aluminum) or omit it entirely.
Magnetic armour causes high power losses due to eddy currents in AC systems.
Single core cables for DC applications may use steel armour as there is no time-varying flux.
Non-magnetic materials like aluminum are used if armouring is mandatory for mechanical strength in single core AC cables.
Prevents overheating of the cable insulation
Increases overall transmission efficiency
Reduces derating factor requirements
Lower mechanical protection if no armour is provided
Higher risk of damage from external mechanical impacts
Low voltage distribution
Substation feeder cables
Underground transmission lines
Option B is incorrect because non-armoured cables are flexible, but that is a secondary benefit, not the reason for avoiding armour.
Option C is irrelevant as hygroscopic properties are managed by the lead sheath or moisture barrier, not the armour.
A is correct тАФ Single core cables avoid magnetic armour to prevent high eddy current and hysteresis losses caused by the alternating magnetic field.
Always remember that for 3-core cables, the net magnetic field is zero at any instant, so magnetic armouring does not cause these losses; this is unique to single core AC cables.