Join 60,000+ competitive exam aspirants
Solid earthing is done for voltage below
400 V
600 V
33 kV
66 kV
33 kV
Solid earthing refers to connecting the neutral point of a star-connected transformer or generator directly to the ground without any intentional impedance. This method is predominantly used for low-voltage systems and medium-voltage systems up to 33 kV to ensure effective fault clearing and system stability.
Solid earthing refers to connecting the neutral point of a star-connected transformer or generator directly to the ground without any intentional impedance. This method is predominantly used for low-voltage systems and medium-voltage systems up to 33 kV to ensure effective fault clearing and system stability.
IfтАЛ=Z1тАЛ+Z2тАЛ+Z0тАЛVphтАЛтАЛ тАФ where IfтАЛ is the single line-to-ground fault current for a solidly grounded system
VneutralтАЛтЙИ0 тАФ characteristic of solid earthing during normal operation
In solid earthing, the neutral path offers minimal impedance, allowing a high fault current to flow during a line-to-ground fault. This high magnitude current is easily detected by protective relays, which trigger circuit breakers to isolate the faulty section rapidly. For higher voltages, solid earthing is avoided because the excessive fault current could cause immense mechanical stress on equipment and interference in communication circuits.
Solid earthing provides the lowest possible impedance path for fault currents.
It limits transient overvoltages and prevents floating neutrals.
Commonly used in distribution networks up to 33 kV.
High fault currents require robust circuit breakers for interruption.
Simplest and cheapest method
Effective suppression of overvoltages
Facilitates easy detection of earth faults
High fault current causes severe equipment damage
Induces interference in nearby telecommunication lines
High mechanical stress on windings during faults
Low voltage distribution systems (415V)
33 kV distribution substations
Above 33 kV, systems typically employ resistance or reactance grounding to limit fault current damage.
Option 400 V and 600 V represent standard low voltage levels where solid earthing is mandatory for personnel safety.
C is correct тАФ Solid earthing is standard practice for voltage systems up to 33 kV to maintain neutral stability and provide reliable fault detection.
Always remember that as voltage increases, the focus shifts from solid grounding to impedance grounding to mitigate the thermal and mechanical impact of high-magnitude ground faults.