The electrostatic stress in underground cables is
Same at the conductor and the sheath
Minimum at the conductor and maximum at the sheath
Maximum at the conductor and minimum at the sheath
Zero at the conductor as well as on the sheath
Maximum at the conductor and minimum at the sheath
In an underground cable, the electrostatic stress (electric field intensity) is non-uniformly distributed across the dielectric insulation. It is inversely proportional to the radius r from the center of the conductor, resulting in the highest stress at the conductor surface and the lowest stress at the inner surface of the lead sheath.
In an underground cable, the electrostatic stress (electric field intensity) is non-uniformly distributed across the dielectric insulation. It is inversely proportional to the radius r from the center of the conductor, resulting in the highest stress at the conductor surface and the lowest stress at the inner surface of the lead sheath.
gmaxтАЛ=rln(R/r)VтАЛ тАФ Stress at conductor surface
gminтАЛ=Rln(R/r)VтАЛ тАФ Stress at sheath surface
The electric field intensity g at a distance r from the center of a cable conductor is given by g=rln(R/r)VтАЛ, where V is the potential difference, r is the radius of the conductor, and R is the inner radius of the sheath. Since the denominator involves r, as r increases from the conductor radius to the sheath radius R, the value of g decreases. Therefore, the gradient is maximum at r=r (conductor surface) and minimum at r=R (sheath surface).
Electrostatic stress is inversely proportional to the radial distance r.
Non-uniform distribution is a limiting factor for cable insulation thickness.
Stress grading is often required in high-voltage cables to equalize this field.
Improved understanding of insulation failure mechanisms
Basis for calculating dielectric strength requirements
Leads to higher stress concentrations at the conductor
Requires grading techniques for very high voltage ratings
Underground transmission cable design
HVDC and HVAC cable insulation selection
The ratio of gmaxтАЛ/gminтАЛ=R/r. For economical design, this ratio is typically kept around 2.718.
Option B is the inverse of the actual physical behavior.
Option A is incorrect because the potential gradient is not uniform.
C is correct тАФ The electrostatic stress in an underground cable is maximum at the conductor surface and decreases as the distance from the center increases, reaching its minimum at the inner surface of the sheath.
Always remember that in cylindrical geometries like cables, the field is strongest where the curvature is highest (the center conductor).