Which among the following cables are generally suited for the voltages upto 11 kV?
Belted cables
Screened cables
Pressure cables
None of these
Belted cables
Belted cables are primarily used for low and medium voltage applications, specifically up to 11 kV. In these cables, the insulation consists of impregnated paper applied in layers around each conductor, with an overall belt of impregnated paper encompassing all three conductors.
Belted cables are primarily used for low and medium voltage applications, specifically up to 11 kV. In these cables, the insulation consists of impregnated paper applied in layers around each conductor, with an overall belt of impregnated paper encompassing all three conductors.
EmaxтАЛ=3тАЛтЛЕrтЛЕln(R/r)VтАЛ тАФ Electric stress calculation for underground cables
In belted cables, the electric field is not purely radial because the filler material between the cores has a different permittivity than the paper insulation. As voltage levels exceed 11 kV, the tangential stress becomes excessive, leading to electrical breakdown of the paper insulation. Therefore, these cables are limited to lower voltage ranges.
Belted cables use a common impregnated paper belt over three cores.
They are restricted to 11 kV due to high tangential stress in the filler material.
Screened cables (H-type, S.L. type) are preferred for higher voltages (22 kV to 66 kV).
Pressure cables (Oil or Gas filled) are used for voltages beyond 66 kV.
Low cost compared to screened cables
Simple construction
Suitable for distribution networks
Presence of tangential electrical stress
Increased risk of dielectric breakdown at higher voltages
Not suitable for high-voltage transmission
Underground distribution systems
Industrial low-voltage power supply
| Feature | Belted Cable | Screened Cable |
|---|---|---|
Voltage Rating | Up to 11 kV | 22 kV to 66 kV |
The core insulation of belted cables is typically impregnated paper.
Option B (Screened cables) are used for higher voltages (up to 66 kV) as they employ metallic screens to ensure radial electric stress.
Option C (Pressure cables) utilize oil or gas under pressure to suppress ionization, used for 66 kV and above.
A is correct тАФ Belted cables are specifically designed for low and medium voltage transmission up to 11 kV, where tangential stress is manageable.
Always remember the hierarchy: Belted (<= 11 kV) < Screened (up to 66 kV) < Pressure (> 66 kV) for underground power cable selection.