Join 60,000+ competitive exam aspirants
Why is the single core cables not provided with armouring?
Avoids excessive loss in the armour
Make the cable more flexible
Make the cable non-hygroscopic
None of these
Avoids excessive loss in the armour
Single core cables carry AC current that creates a time-varying magnetic field around the conductor. If a magnetic material (like steel wire armouring) were used, this field would induce eddy currents in the armour, leading to significant power losses and overheating.
Single core cables carry AC current that creates a time-varying magnetic field around the conductor. If a magnetic material (like steel wire armouring) were used, this field would induce eddy currents in the armour, leading to significant power losses and overheating.
PlossтАЛ=Iinduced2тАЛ├ЧRarmourтАЛ тАФ Power loss calculation due to induced current
E=тИТdtd╬жтАЛ тАФ Faraday's Law responsible for the induced EMF in the armour
According to Faraday's law of electromagnetic induction, the alternating current in the conductor induces an electromotive force (EMF) in the surrounding metallic armour. Since the armour forms a closed magnetic loop around the single conductor, these induced voltages drive substantial circulating currents (eddy currents), resulting in I2R power losses and potential cable damage.
Armouring in single-core cables is replaced by non-magnetic materials (like aluminium tape or wire) if mechanical protection is required.
Eddy current losses increase the effective resistance of the cable, reducing its current-carrying capacity (ampacity).
In three-core cables, the net magnetic flux produced by the three phases is nearly zero, which is why they can be safely armoured with steel.
Prevents overheating of cables
Maximizes current-carrying efficiency
Higher risk of mechanical damage if non-magnetic materials are not used
Less rugged compared to steel-armoured multi-core cables
AC power distribution in conduits
High-voltage single-core transmission systems
| Feature | Single-Core Cable | Three-Core Cable |
|---|---|---|
Magnetic Material Armour | Excessive Eddy Current Loss | Negligible Loss |
Standard: IS 7098 (Part 1 & 2) specifies construction requirements for XLPE cables.
Option B (Flexibility) is secondary; the primary constraint for avoiding steel armour in single-core cables is electromagnetic loss.
Option C (Non-hygroscopic) relates to cable sheath material, not the function of armouring.
A is correct тАФ Single core cables avoid steel armouring to prevent the induction of circulating eddy currents caused by the surrounding time-varying magnetic field.
Always remember that in three-phase systems, the vector sum of currents is zero, neutralizing the magnetic fluxтАФthis is the fundamental reason why multi-core cables can use steel armour while single-core cannot.