The output current corresponding to maximum efficiency for a transformer having a core loss of 100 W and equivalent resistance referred to secondary of 0.25 тДж is ....... ampere.
20
25
400
20
The maximum efficiency of a transformer occurs when the variable copper loss equals the constant core loss. By equating I2ReqтАЛ=PcoreтАЛ, the output current for maximum efficiency is determined.
The maximum efficiency of a transformer occurs when the variable copper loss equals the constant core loss. By equating I2ReqтАЛ=PcoreтАЛ, the output current for maximum efficiency is determined.
PcoreтАЛ=I2ReqтАЛ тАФ Condition for maximum efficiency
I=ReqтАЛPcoreтАЛтАЛтАЛ тАФ Output current formula
In a transformer, core losses (hysteresis and eddy current) are constant regardless of load, while copper losses (I2R) vary with the square of the current. Efficiency is defined as Output+LossesOutputтАЛ. Mathematical derivation shows that the derivative of losses with respect to current is zero when I2R=PcoreтАЛ, which represents the point of maximum efficiency.
Core loss is constant for all load values.
Copper loss is directly proportional to the square of the load current.
Efficiency is maximized when constant losses equal variable losses.
Optimizes transformer performance.
Provides a design target for full-load efficiency.
Max efficiency may not coincide with rated load capacity.
Requires precise determination of internal resistances.
Transformer design for power distribution.
Energy efficiency auditing in electrical systems.
Given: Core loss PcтАЛ=100┬аW, Resistance R=0.25┬а╬й.
Calculation: I=100/0.25тАЛ=400тАЛ=20┬аA.
Option D is a distractor, representing the value inside the square root before the operation is finalized.
A is correct тАФ The maximum efficiency condition I2R=PcoreтАЛ yields I=100/0.25тАЛ=20┬аA.
Always verify if the resistance given is referred to the primary or secondary side, as this dictates which side current will be calculated.