The positive sequence component of voltage at the point of fault is zero when it is a
phase fault
L-L fault
L-L-G fault
L-G fault
phase fault
In a three-phase system, a 'three-phase fault' (often referred to as a balanced or symmetrical fault) involves all three phases being shorted together, with or without ground. Under the assumption of perfect symmetry, the positive sequence voltage V1тАЛ at the point of fault becomes zero, while the negative and zero sequence components remain zero due to the balanced nature of the fault.
In a three-phase system, a 'three-phase fault' (often referred to as a balanced or symmetrical fault) involves all three phases being shorted together, with or without ground. Under the assumption of perfect symmetry, the positive sequence voltage V1тАЛ at the point of fault becomes zero, while the negative and zero sequence components remain zero due to the balanced nature of the fault.
VfтАЛ=V1тАЛ+V2тАЛ+V0тАЛ тАФ The sequence component decomposition of the fault voltage
ZthтАЛ=IfaultтАЛVprefaultтАЛтАЛ тАФ The Thevenin equivalent impedance calculation for symmetrical faults
In a symmetrical fault (three-phase fault), the fault currents are IaтАЛ,IbтАЛ,IcтАЛ with IaтАЛ+IbтАЛ+IcтАЛ=0 and IaтАЛ=a2IbтАЛ=aIcтАЛ. Since the system is balanced, the sequence network reduces to only the positive sequence network. At the point of a bolted three-phase fault, the voltage at the fault is clamped to ground (or zero potential), leading to V1тАЛ=V2тАЛ=V0тАЛ=0.
Symmetrical faults involve all three phases equally.
Positive sequence voltage is the only component present in balanced systems; during a 3-phase fault, this component drops to zero at the fault point.
Unsymmetrical faults (L-G, L-L, L-L-G) involve non-zero sequence components at the fault point.
Simplifies power system analysis to a single-phase equivalent circuit.
Easier calculation of short-circuit MVA capacity.
Rare occurrence compared to unsymmetrical faults.
Most severe stress on equipment and circuit breakers.
Used for sizing circuit breakers for maximum interrupting capacity.
Setting relay trip thresholds.
Option B (L-L) involves negative sequence voltage.
Option D (L-G) involves all three sequence networks connected in series.
Option C (L-L-G) involves sequence networks connected in parallel.
A is correct тАФ The positive sequence voltage at the fault point is zero specifically during a balanced three-phase fault.
Remember that for any symmetrical (balanced) condition, negative and zero sequence components are zero, but only in a bolted 3-phase fault does the positive sequence component also vanish at the fault location.