The power delievered to a 3-phase load can be measured by the use of two wattmeters only when
load is balanced
load is unbalanced
phase load is connected to the source of 3-wires
phase load is connected to the source of 4-wires
phase load is connected to the source of 3-wires
The two-wattmeter method is a universal technique for measuring power in a 3-phase system provided that the system is a 3-wire system. This is based on Blondel's Theorem, which states that for an N-conductor system, N-1 wattmeters are required to measure the total power.
The two-wattmeter method is a universal technique for measuring power in a 3-phase system provided that the system is a 3-wire system. This is based on Blondel's Theorem, which states that for an N-conductor system, N-1 wattmeters are required to measure the total power.
PtotalтАЛ=W1тАЛ+W2тАЛ тАФ Total power in 3-phase 3-wire system
P=3тАЛVLтАЛILтАЛcos(╧Х) тАФ Power for balanced load (Reference)
According to Blondel's Theorem, the total power in a system of N conductors can be measured by connecting the current coils of N-1 wattmeters in series with N-1 lines and connecting the potential coils between the respective line and the remaining conductor (the common return path). In a 3-phase 3-wire system, N=3, so NтИТ1=2 wattmeters are sufficient, regardless of whether the load is balanced or unbalanced or connected in star or delta.
Blondel's theorem is valid for any waveform and any load condition (balanced or unbalanced).
If a neutral wire is present (4-wire system), 3 wattmeters are required to measure total power.
The two-wattmeter method is independent of the star or delta configuration of the load.
Reading of one wattmeter may become negative if the power factor is less than 0.5 (lagging).
Works for both balanced and unbalanced loads.
Applicable to both star and delta connected systems.
Requires three wires only; cannot be used for 4-wire systems without modification.
Calculation of power factor requires both readings.
Industrial 3-phase motor power monitoring.
Utility metering in 3-phase 3-wire distribution.
In a 4-wire system, if the load is balanced, the neutral current is zero, and 2 wattmeters would technically suffice; however, for general unbalanced cases, 3 wattmeters are mandatory.
Option A and B are incorrect because the number of wattmeters depends on the number of wires, not the load balance.
C is correct тАФ The two-wattmeter method is a direct application of Blondel's Theorem for measuring power in any 3-phase 3-wire system.
Always remember that in electrical instrumentation, the number of measuring elements is determined by the number of lines (conductors) in the circuit, not the nature of the load impedance.