The primary of a 220/110 V, 50 Hz transformer is connected to a 110V, 60 Hz supply. The secondary output voltage is
A
55
Zero
220
55
The output voltage of a transformer is directly proportional to the applied voltage and the turns ratio, and inversely proportional to the frequency for a constant flux density. Since the transformer is being operated at half the rated primary voltage (110V instead of 220V) while maintaining the same volts-per-turn relationship to avoid saturation, the secondary voltage scales proportionally to the applied input.
The output voltage of a transformer is directly proportional to the applied voltage and the turns ratio, and inversely proportional to the frequency for a constant flux density. Since the transformer is being operated at half the rated primary voltage (110V instead of 220V) while maintaining the same volts-per-turn relationship to avoid saturation, the secondary voltage scales proportionally to the applied input.
E=4.44fNphimтАЛ тАФ EMF equation of a transformer
racV1тАЛV2тАЛ=racN1тАЛN2тАЛ тАФ Ideal transformer turns ratio
The transformer EMF equation is E=4.44fNphimтАЛ. Given the supply voltage V1тАЛ is 110V (half of rated 220V) and frequency f is 60Hz, the magnetic flux phimтАЛ adjusts to V/f. As the ratio of turns N1тАЛ/N2тАЛ remains constant (2:1), the output V2тАЛ becomes (VappliedтАЛ/VratedтАЛ)imesVrated_secondaryтАЛ=(110/220)imes110=55V.
The transformer turns ratio is determined by the design and is fixed as 220/110=2.
Operating at a different frequency affects the magnetic flux, but the voltage ratio is primarily dictated by the turns ratio.
Reducing input voltage by half results in the output voltage reducing by half.
Predictable linear voltage scaling
Maintains isolation properties
Flux density changes with frequency shifts
Potential for core saturation if frequency is too low
Voltage level matching
Impedance matching in power systems
The change in frequency from 50Hz to 60Hz changes the flux density BmтАЛ by a factor of (50/60)imes(110/220)=5/12.
Option A is incorrect as it is incomplete; Option C is incorrect as the transformer still functions; Option D is incorrect as it implies no voltage drop.
B is correct тАФ The secondary voltage scales linearly with the input voltage, resulting in 110imes(110/220)=55V.
Always check the Volts-per-Hertz (V/f) ratio when frequency deviates from the nameplate rating to determine if the core will saturate.