Join 60,000+ competitive exam aspirants
The purpose of guard ring in transmission line is to
Reduce the earth capacitance of lowest unit
Increase the earth capacitance of the lowest unit
Reduce the transmission line losses
None of above
Reduce the earth capacitance of lowest unit
A guard ring is a metal ring electrically connected to the cross-arm or the metal structure of the tower, positioned around the lowest unit of a suspension insulator string. Its primary purpose is to balance the voltage distribution across the string by reducing the stray (shunt) capacitance of the lowest unit, which typically experiences the highest electrical stress.
A guard ring is a metal ring electrically connected to the cross-arm or the metal structure of the tower, positioned around the lowest unit of a suspension insulator string. Its primary purpose is to balance the voltage distribution across the string by reducing the stray (shunt) capacitance of the lowest unit, which typically experiences the highest electrical stress.
VstringтАЛ=V1тАЛ+V2тАЛ+...+VnтАЛ тАФ Sum of voltages across insulator discs
IshuntтАЛ=VтЛЕj╧ЙCshuntтАЛ тАФ Charging current due to stray earth capacitance
In a string of suspension insulators, the voltage distribution is non-uniform due to the presence of shunt capacitance between each insulator unit and the grounded tower. The lowest unit (nearest the conductor) carries the maximum voltage stress. By adding a guard ring, an additional capacitance is introduced between the conductor and the guard ring, which effectively neutralizes the current flowing through the stray capacitance to the tower. This makes the charging current uniform across all insulator discs, leading to a more linear voltage distribution.
The lowest insulator disc in an unstressed string carries the maximum voltage.
A guard ring introduces a compensating capacitance (CgтАЛ) that effectively cancels the effect of shunt capacitance (CshuntтАЛ).
It improves string efficiency by ensuring V1тАЛтЙИV2тАЛтЙИVnтАЛ.
Commonly used in HV and EHV transmission lines using suspension insulators.
Uniform voltage distribution across insulator discs
Prevents local dielectric breakdown (flashover) of the bottom unit
Increases the overall string efficiency
Adds weight to the insulator string assembly
Requires additional installation cost and maintenance
May be susceptible to corona if not designed with smooth rounded edges
Suspension type insulator strings for 132kV and above lines
Bushings of high voltage transformers
High voltage laboratory equipment
String efficiency is defined as: ╬╖=n├ЧVoltageacrossthelowestunitVoltageacrossthewholestringтАЛ├Ч100%.
Option B is incorrect because increasing shunt capacitance would further degrade voltage distribution and lower string efficiency.
Option C is incorrect because guard rings do not significantly reduce active power losses; they are strictly for electric field management.
A is correct тАФ The guard ring reduces the effect of earth (shunt) capacitance on the lowest insulator unit, thereby balancing the voltage distribution.
Always remember that in a string of insulators, the unit closest to the line conductor is always at the highest potential; therefore, devices like guard rings are placed specifically to protect this unit.