Join 60,000+ competitive exam aspirants
The severity of line to ground and three-phase faults at the terminals of an unloaded synchronous generator is to be same. If the terminal voltage is 1.0 pu, ZтВБ = ZтВВ = j0.1 pu and ZтВА = j0.05 pu for the alternator, then the required inductive reactance for neutral grounding is
0.0166 pu
0.05 pu
0.1 pu
0.15 pu
0.0166 pu
To equate the fault currents, the magnitude of the three-phase fault current (I3╧ХтАЛ=Z1тАЛVтАЛ) is set equal to the line-to-ground fault current (ILGтАЛ=Z1тАЛ+Z2тАЛ+Z0тАЛ+3ZnтАЛ3VтАЛ). By solving this equality with the given sequence impedances and ZnтАЛ=jXnтАЛ, we determine the required grounding reactance.
To equate the fault currents, the magnitude of the three-phase fault current (I3╧ХтАЛ=Z1тАЛVтАЛ) is set equal to the line-to-ground fault current (ILGтАЛ=Z1тАЛ+Z2тАЛ+Z0тАЛ+3ZnтАЛ3VтАЛ). By solving this equality with the given sequence impedances and ZnтАЛ=jXnтАЛ, we determine the required grounding reactance.
I3╧ХтАЛ=Z1тАЛVтАЛ тАФ Three-phase fault current
ILGтАЛ=Z1тАЛ+Z2тАЛ+Z0тАЛ+3ZnтАЛ3VтАЛ тАФ Line-to-ground fault current
In a symmetrical three-phase fault, only the positive sequence impedance limits the fault current. In a line-to-ground fault, the fault current depends on the series combination of positive, negative, and zero sequence impedances, where the neutral grounding impedance ZnтАЛ is amplified by a factor of 3 in the zero-sequence network.
For solid grounding, ZnтАЛ=0.
Neutral reactance XnтАЛ is used to limit the magnitude of LG faults to protect equipment.
Sequence networks are connected in parallel for LG faults.
Base values for per-unit system must be consistent across all impedances.
Limits fault currents to prevent equipment damage
Reduces mechanical stress on generator windings
Increases overvoltage during LG faults
Complicates relay coordination
Synchronous generator protection
Power system stability control
Calculation: 1/0.1=3/(0.1+0.1+0.05+3XnтАЛ)тЗТ10=3/(0.25+3XnтАЛ)тЗТ2.5+30XnтАЛ=3тЗТ30XnтАЛ=0.5тЗТXnтАЛ=0.0166pu.
Option B (0.05) is the zero sequence reactance, not the neutral grounding reactance.
A is correct тАФ The required neutral grounding reactance is 0.0166 pu to ensure the LG fault current magnitude equals the three-phase fault current magnitude.
Always remember the factor of 3 for neutral impedance (3ZnтАЛ) in the zero-sequence network diagram for unbalanced faults.