Join 60,000+ competitive exam aspirants
The zero sequence current of a generator for line to ground fault is j2.4 pu. Then the current through the neutral during the fault is
j2.4 pu
j0.8 pu
j7.2 pu
j0.24 pu
j7.2 pu
Given: Zero sequence current of the generator I0 = j2.4 pu
Zero sequence current of the generator I0 = j2.4 pu
In=3×I0
Identify the relationship
In a three-phase system, the current flowing through the neutral (In) during an unsymmetrical fault is the sum of the sequence currents of the three phases.
In=Ia+Ib+Ic
Apply Sequence Component theory
The zero sequence current is defined as I0=31(Ia+Ib+Ic). Therefore, the total neutral current is equal to three times the zero sequence current.
In=3×I0
Calculate the result
Given the zero sequence current I0=j2.4 pu, substitute this value into the formula to find the neutral current.
In=3×(j2.4)=j7.2 pu
C is correct because the neutral current is defined as three times the zero sequence current, resulting in j7.2 pu.
This concept is vital for designing grounding schemes; note that the neutral current is zero in balanced systems but becomes significant during single-line-to-ground faults.