Join 60,000+ competitive exam aspirants
The voltage rating of a multiple shell pin insulator unit cannot be increased beyond a limiting value by increasing the number of shells, because
Internal voltage distribution between shells becomes unequal
Leakage path resistance starts diminishing
Disruptive critical voltage for the material of the insulator is reached
Puncture voltage of the material of the insulator is reached
Internal voltage distribution between shells becomes unequal
In a multiple-shell pin insulator, the voltage distribution across different shells is determined by the capacitive reactance of each shell. As more shells are added to increase the voltage rating, the stray capacitances to the ground and the cross-arm become more dominant than the self-capacitance, leading to highly unequal voltage distribution.
In a multiple-shell pin insulator, the voltage distribution across different shells is determined by the capacitive reactance of each shell. As more shells are added to increase the voltage rating, the stray capacitances to the ground and the cross-arm become more dominant than the self-capacitance, leading to highly unequal voltage distribution.
VshellтАЛ=j╧ЙCselfтАЛIтАЛ
VtotalтАЛ=тИСi=1nтАЛViтАЛ
Each shell acts as a capacitor in a series-parallel network. Due to the proximity of the metal pin and the cross-arm, stray capacitances (CsтАЛ) exist between the shells and the ground. Because the capacitance values are not uniform and stray effects accumulate with more units, the outer shells experience higher electrical stress. Eventually, increasing the number of shells yields diminishing returns because the added outer shells cannot share the voltage equally, causing local breakdown of air near the conductor.
Voltage distribution in pin insulators is non-uniform due to stray capacitances.
The insulator capacitance decreases as the distance from the conductor increases.
Adding more shells does not linearly increase the puncture strength due to the potential gradient.
The efficiency of a multi-shell insulator decreases as the number of units increases.
Improved arc distance in compact designs
Enhanced mechanical strength
Increased weight and cost
Potential for unequal stress distribution leading to corona discharge
Distribution lines up to 33kV
Sub-transmission systems
Standard pin insulators are generally used only up to 33kV due to the aforementioned limitations of unequal stress.
Option B is incorrect because increasing shells actually increases the total leakage path length, not diminishes it.
Option D is incorrect because puncture voltage is a material property that is independent of the number of shells in a string-like arrangement of layers.
A is correct тАФ The unequal voltage distribution caused by stray capacitances makes the addition of shells ineffective beyond a certain limit.
Always remember that in series-connected electrical insulation, non-uniform stress distribution is the primary limiting factor, often solved in practice by using grading rings or capacitive grading.